Laserfiche WebLink
Fuel Control Service <br /> 9725 Mission Gorge Rd.#156 <br /> Santee,CA 92071 <br /> 619-562-3255 <br /> SUMMARY OF TEST EVALUATION REPORT <br /> The US Test 2000 System declares a tank to be leaking when the measured leak rate exceeds <br /> the threshold of.05 gph and has a probability of false alarm of<1%and a probability of <br /> detection of>99%.FCS assumes no responsibility for product leakage.Our responsibility <br /> extends only to the tesing of tanks as to tight or not tight,as of the date and levels tested. <br /> Customer: Stockton USD <br /> Site ID: <br /> Site Address: 944 N.El Pinal Dr. <br /> City: Stockton <br /> State: CA. <br /> Zip: 95205 <br /> TEST RESULTS-LEVEL TEST RESULTS-ULLAGE <br /> 1.Die 2 .009643 GPH PASS 1.Die 2 SN: .04 GPH PASS <br /> 2.Reg Unl .016303 GPH PASS 2.Reg Unl SN: .03 GPH PASS <br /> 3. 3. <br /> 4. 4. <br /> 5. 5. <br /> 6. 6. <br /> LINE TEST RESULTS LINE LEAK DETECTOR <br /> 1.Reg Unl.0071 GPH PASS 1.PASS <br /> 2.Die 2.0143 GPH PASS 2.PASS <br /> 3. 3. <br /> 4. 4. <br /> 5. 5. <br /> 6. 6. <br /> COMMENTS <br /> Pressure system. D/Wall tanks. <br /> TANK INFORMATION <br /> TANK# 1. 2. 3. 4. 5. 6. <br /> DIAMETER 110 110 <br /> VOLUME 20000 15000 <br /> PRODUCT D-2 RU <br /> TANK TYPE SG SG <br /> LEVEL 97 84 <br /> WATER LVL 0 0 <br /> GRND WATER BT BT <br /> TECHNICIAN Steve Young LIC.# 90-1291 CERT# DATE: 11/11/98 <br />