Laserfiche WebLink
_vVizi <br /> /NTERNAT/OVAL <br /> 1 INTRODUCTION <br /> 1.1 PURPOSE <br /> The purpose of this(preliminary design report is to provide the process design for The Wine Cup <br /> Motor Coach Resort Wastewater Treatment Plant (WCMCRWWTP). This proposal consists of <br /> three sections, including introduction, packaged WCMCRWWTP design, and unit process design. <br /> The appendices include process design calculations, design drawings, and mechanical <br /> equipment specifications. <br /> 1.2 DESIGN BASIS <br /> `► The WCMCRWWTP is designed and will be built to receive and dispose of the domestic sewage <br /> 4' from Wine Cup Motor Coach Resort, Acampo, California. Wine Cup Motor Coach Resort consists <br /> V of 52 standard space and 95 pull through spaces. The gated park will have 147 RV spots - <br /> �+ many of them designed to be large enough to accommodate expansive motor coaches - as well <br /> `• as a swimming pool with waterfall, spa, sauna, clubhouse, exercise room, game room, small <br /> t. grocery mini-mart, four shower/restroom buildings, laundry facilities and hook ups for water, <br /> sewer, electricity, telephone, satellite TV and wireless Internet. <br /> The average dry weather design flow for the WCMCRWWTP will bey 25,000 gallons per day F <br /> (gpd). The design criteria is summarized in Table 1, based upon the information gathered from <br /> the Client. <br /> �A' Table 1 Design Flow Conditions and Effluent Quality <br /> L <br /> ITEMS INFLUENT EFFLUENT <br /> Average dry weather flow d 25,000 <br /> V BODS (mg/L 350 10 <br /> TSS (mg/L 250 10 <br /> Turbidity NTU <2 <br /> �4/ TN (mg/L 10 <br /> 46 TKN (mg/L 40 <br /> r.. NH3-N (mg/L 25 2.0 <br /> Total Coliform (MPN) :52.2 colonies/100 mL in 7 days <br /> 11116 <_23 colonies/100 mL in any 30 days <br /> :5100 colonies/100 mL in any sample <br /> The WCMCRWWTP shall function to remove both organic matter (BODS) and the total nitrogen <br /> `- (TN). Generally, the organic loading of the packaged wastewater treatment plant is based upon <br /> a design average flow and is used for sizing the biological system. The hydraulic loading of the <br /> Wine Cup Motor Coach Resort WWTP Page 2 of 10 8/22/2007 <br /> Preliminary Design Report <br />