Laserfiche WebLink
California Freight Safety Manual and IIPP <br /> 9. Travel distance from any point of the protected area to the nearest fire extinguisher shall <br /> not exceed 75 feet. <br /> 10. At least one fire extinguisher, rated not less than 2A, shall be provided on each floor. In <br /> multi-story buildings, at least one fire extinguisher shall be located adjacent to the stairway <br /> at each floor level. <br /> 11. A fire extinguisher, rated not less than 1013, shall be provided within 50 feet of wherever <br /> more than 5 gallons of flammable or combustible liquids or 5 pounds of flammable gas are <br /> being used on the job site. This requirement does not apply to the integral fuel tanks of <br /> motor vehicles. <br /> 12. Portable fire extinguishers shall be inspected monthly, or at more frequent intervals by the <br /> employer, and serviced at least annually by a person licensed or registered by the State Fire <br /> Marshal. NOTE: Inspection is a "quick check" that an extinguisher is available and will <br /> operate. It is intended to give reasonable assurance that the extinguisher is fully charged <br /> and operable. This is done by seeing that it is in its designated place, that it has not been <br /> actuated or tampered with, and that there is no obvious or physical damage or condition to <br /> prevent operation. <br /> 13. Suitable fire control devices, such as portable fire extinguishers, shall be available at <br /> locations where flammable or combustible liquids are stored. <br /> 14. At least one portable fire extinguisher, having a rating of not less than 20-B units, shall be <br /> located outside of, but not more than 10 feet from, the door opening into any room used <br /> for flammable liquid storage. <br /> 15. At least one portable fire extinguisher, having a rating of not less than 20-B units, shall be <br /> located not less than 25 feet, nor more than 75 feet, from any flammable liquid storage <br /> area located outside. <br /> Revised January 1,2019 Page 55 <br />