Laserfiche WebLink
Hazardous Waste Tank System RECD J U L 2 0 2015 I+ March <br /> Written Assessment per CCR Title 22 <br /> Applied Aerospace Structures, Inc.. Stockton, CA 95206 2015 <br /> Tank: Acid Waste Neutralization Tank 1 <br /> Rectangular, Open Top <br /> Material of Construction: polypropylene <br /> Shell Height, in 48.00 <br /> Shell Length, in 120.00 <br /> Working Volume, gal 670.00 <br /> S.G. of contents 1.00 <br /> Tank Wall Thickness, in 0.36 <br /> Total Weight of Tank and Contents, lbs. 5924.00 <br /> Lat 38.6 <br /> Lon -121.4 <br /> Overturning Moment Arm, in 32.00 <br /> Resisting Moment Arm, in 15.00 <br /> Sds 0.69 <br /> Importance Factor 1.00 <br /> Fp, ASCE 7-05, 15.4-2 1226.27 <br /> Overturning Moment inlbf 39240.58 <br /> Resisting Moment, inlbf 88860.00 <br /> Overturning Safety Factor- No Tension 2.26 <br /> Shear Strength of Anchor Lbs. 3432.00 <br /> #of Anchors 0.00 <br /> Factor of Safety for Shear 0.00 <br /> Seismic/Anchorrina, findings: The tank as desi and operated and the <br /> containment area in which it is located are adeq ly anchored and are <br /> seismically sound. Initials: <br /> Strandberg Associates 1(866) 388-0404 rwaterq y(q)_rwaterguy.com 16 <br />