Laserfiche WebLink
Hazardous Waste Tank System September <br /> Final Written Assessment per CCR Title 22 2015 <br /> Stockton Dodge. Stockton,CA 95212 <br /> 1 <br /> Foundation Analysis, Waste Oil Tank <br /> Soil Type: Clay Sandy, Allowable Pressure, psf 1500.00 <br /> area of foundation, ft2 30.83 <br /> depth of concrete, in 6.00 <br /> weight of concrete, lbs. 2308.80 <br /> weight of tank and contents, lbs. 5924.00 <br /> total weight on soil, lbs. 8232.80 RECEIVED <br /> pressure on soil, sf 267.01 <br /> Safety Factor 5.62 DEC 21 2015 <br /> Soil is Okay for Foundation <br /> Concrete Analysis 2500.00 ENVIRONMENTAL HEALTH <br /> fc', psi PERMIT/SERVICES <br /> br 0.70 <br /> Cr 1.00 <br /> loaded area, in2 720.00 <br /> Foundation Bearing Capacity, Fb, lbs. 535500.00 <br /> 1 Combined weight of tank and contents, lbs. 5924.00 <br /> Safety Factor 90.40 <br /> Foundation is Okay for tank. <br /> i <br /> n <br /> Integrity testing fin ngs: Based on the above noted integrity test and the <br /> results obtained fro at test, the tank has sufficient integrity for its intended <br /> use. Initials.- <br /> Strandberg <br /> nitials:Strandberg Associates 1(866) 388-0404 rwaterpuy(cDrwaterauy com 14 <br />