Laserfiche WebLink
Hazardous Waste Tank System September <br /> Final Written Assessment per CCR Title 22 <br /> Stockton Dodge.Stockton,CA 95212 2015 <br /> Tank: Waste Antifreeze Tank <br /> Cylindrical, Vertical Closed Top, Flat Bottom, Diked <br /> Material of Construction: HDPE RECEIVED <br /> Shell Height, in 51.00 DEC 21 2015 <br /> Shell Diameter, in 36.00 <br /> Working Volume, gal 193.00 <br /> S.G. of contents 1.05 ENVIRONMENTAL HEALTH <br /> Tank Wall Thickness, in 0.30 PEE+IAIT/SERVICES <br /> Total Weight of Tank and Contents, lbs. 1689.00 <br /> Overturning Moment Arm, in 22.00 <br /> Resisting Moment Arm, in 24.00 <br /> Sds 0.78 <br /> Importance Factor 1.00 <br /> Fp, ASCE 7-10, 15.4-2 395.23 <br /> Overturning Moment inlbf 8694.97 <br /> Resisting Moment, inlbf 40536.00 <br /> Overtuming Safety Factor- No Tension 4.66 <br /> Shear Strength of Anchor. Lbs. 4760.00 <br /> #of Anchors 1.00 <br /> Factor of Safety for Shear 12.04 <br /> Seismic/Anchoring findings: The tank as d s' ned and operated and the <br /> containment area in which it is located areae ately anchored and are <br /> seismically sound. Initials: <br /> Strandberg Associates 1(866) 388-0404 rwaterguv@rwaterguv.com 20 <br />