Laserfiche WebLink
4 <br /> Pace Analytical Services,Inc <br /> r r �, 900 Gemini Avenue <br /> aceAnalyical Houston, TX 77058 <br /> WWW pacelabscom QUALITY CONTROL DATA Phone 2814881810 <br /> Fax 281488 4881 <br /> f° <br /> - Lab Project Number 8524336 <br /> Client Project ID BP Site 11193 <br /> QC Batch 60323 Analysis Method EPA 8015 Modified <br /> QC Batch Method EPA 8015 Modified Analysis Description GAS by Mod 8015 Water <br /> Associated Lab Samples 851719400 <br /> METHOD BLANK 851719802 <br /> Associated Lab Samples 851719400 <br /> Blank Reporting <br /> ' Parameter Units Result Limit Footnotes <br /> Gasoline Range Organics ug/l ND 50 <br /> 1,4 Difluorobenzene (S) % 90 <br /> 4 Bromofluorobenzene (S) % 92 <br /> LABORATORY CONTROL SAMPLE 851719803 <br /> Spike LCS LCS <br /> Parameter Units Conc Result X Rec Footnotes <br /> Gasoline Range Organics ug/l 1000 931 7 93 <br /> 1,4 Difluarobenzene (S) 110 <br /> 4 Bromofluorobenzene (S) 94 <br /> MATRIX SPIKE 8 MATRIX SPIKE DUPLICATE 851720086 851720087 <br /> 851720009 Spike MS MSD MS MSD <br /> Parameter Units Result Conc Result Result X Rec X Rec RPD Footnotes <br /> Gasoline Range Organics ug/l 17 03 1000 00 851 8 896 0 84 88 5 <br /> 1 4-Difluorobenzene (S) 107 108 <br /> 4-Bromofluorobenzene (S) 94 96 <br /> Date 11/15/01 Page 16 <br /> REPORT OF LABORATORY ANALYSIS <br /> This report shall not be reproduced,except in full, <br /> without the written consent of Pace Analytical Services, Inc <br /> ��c W �ccoga+A <br /> O C <br /> A <br /> 4 = <br />