Laserfiche WebLink
Case Narrative C <br /> Client: Environmental Cost Management, Inc. TestAmerica Job ID: 720-53529-1 <br /> Project/Site: Nestle-Ripon <br /> Job ID: 720-53529-1 <br /> Laboratory:TestAmerica Pleasanton <br /> Narrative <br /> Job Narrative <br /> 720-53529-1 <br /> Comments <br /> No additional comments. <br /> Receipt <br /> The samples were received on 11/5/2013 3:15 PM;the samples arrived in good condition,properly preserved and,where required,on ice. <br /> The temperature of the cooler at receipt was 2.9°C. <br /> GC/MS VOA <br /> Method 524.2:The continuing calibration verification(CCV)for Chloroethane and chloromethane associated with batch 143072 recovered <br /> above the upper control limit. The samples associated with this CCV were non-detects for the affected analytes;therefore,the data have <br /> been reported. <br /> Method 524.2:The laboratory control sample(LCS)and/or laboratory control sample duplicate(LCSD)for batch 143072 recovered <br /> outside control limits for the following analytes:Chloroethane and Chloromethane. These analytes were biased high in the LCS and were <br /> not detected in the associated samples;therefore,the data have been reported. <br /> No other analytical or quality issues were noted. <br /> General Chemistry <br /> No analytical or quality issues were noted. <br /> TestAmerica Pleasanton <br /> Page 4 of 45 11/12/2013 <br />