Laserfiche WebLink
CONTRACTORS LICENSE 610#764037 <br /> INSTRUMENTATION --CONTROLS- ELECTRICAL <br /> P O BOX 610, ACAMPO CA 95220 <br /> (209)483-7846--FAX/MESSAGE (209) 339-4571-eric@coopercontrols com <br /> CA OSB CERTIFIED -CWEA CERTIFIED <br /> CALIBRATION REPORT <br /> Customer ATC Associates Service Date 11115!2004 <br /> 1117 Lone Palm Ave , Suite B <br /> Modesto, CA 95351 Project# 2244 <br /> Attention• Mr Drew Van Allen <br /> MANUFACTURER: MSA <br /> MODEL,. 487811 <br /> SERIAL#: 5623 <br /> ITEM SERVICED: LEL Analyzer, 610 N Hunter Street, Stockton CA <br /> DESCRIPTION OF EQUIPMENT LEL Gas Transmitter, 0-40% Hexane= 0-2 6 VDC Alarm Output @ <br /> 10%or 14 VDC wNokagawa Strip Chart Recorder <br /> INITIAL CHECK <br /> INPUT DESIRED DISPLAYED DISPLAY <br /> OUTPUT OUTPUT ERROR <br /> % % % % <br /> 000 000 1043 2608 <br /> 4000 4000 5425 3563 <br /> FINAL CHECK <br /> INPUT DESIRED DISPLAYED DISPLAY <br /> OUTPUT OUTPUT ERROR <br /> % % % % <br /> 000 000 004 010 <br /> 4000 4000 4000 000 <br /> COMMENTS <br /> Calibrated with 40% LEL Hexane in Air Test Gas Set Alarm Output @ 10%or 1 4 VDC Could Not Verify <br /> Auto Shut Down @ 10%due to Broken Burner Control Fan <br /> AS Te nic Date Completed <br /> 11/15I2DD4 <br /> Tom Mannor <br />