HVAC SYSTEM REPORT °2;306 <br /> SYSTEM SUMMARY DATA: FAN NAMEPLATE DATA: PROJECT: <br /> FAN: DESIGN ACTUAL MANUFACTURER CAPTIVE AIRE Jack In The Box <br /> - 3400 N. MacArthur <br /> SUPPLY AIR CFM 1280 1347 MODEL NSAU1-G10 Tracy, CA 94063 <br /> RETURN AIR CFM - - TYPE MAKE UP AIR UNIT <br /> OUTSIDE AIR CFM 1280 1347 SIZE - <br /> FAN RPM - 775 SERIAL NUMBER 500930 SYSTEM: <br /> STATIC PRESSURE. FAN PULLEY DATA: <br /> STATIC PRESSURE- - DIAMETER 6-1/2" MAU - 1 <br /> TOTAL STATIC PRESSURE - SHAFT 3/4" <br /> FILTER STATIC PRESSURE - CLEAN ADJ/FIXED FIXED <br /> MOTOR: MOTOR PULLEY DATA: READINGS BY: <br /> MPS 2.65-2.7 1.85 DIAMETER 3-3/4" <br /> VOLTS/PHASE 208-230/3 213 SHAFT 5/8" DM & TU <br /> HORSEPOWER 3/4 3/4 ADJ/FIXED ADJ <br /> _ RPM 17251 1764 BELT NO. & SIZE (1) AX41 <br /> MOTOR NAMEPLATE DATA: JOB NUMBER: <br /> TEMPERATURE IN: - MANUFACTURER Weg Electric <br /> TEMPERATURE OUT: VOLTS/PHASE 208-230/3 261231 <br /> DROP/RISE: HORSEPOWER 3/4 <br /> MODE: FULL LOAD AMPS 2.65-2.7 ■ , <br /> RPM 1725 <br /> REMARKS: SERVICE FACTOR 1 <br /> CONDENSING UNIT DATA: Z <br /> MANUFACTURER Qco <br /> MODEL - rn <br /> TONNAGE - J o <br /> SERIAL NUMBER - Q w �Lo <br /> M � CV <br /> DIFFUSERS AND GRILLS W co Cl) <br /> Q � <br /> Room Outlet Code Size Required Test Final % o rn z <br /> No. CFM 1 CFM Design X QY o <br /> Hood 1 1 Duct 12" 378 523 412 O O N <br /> Hood 1 2 Duct 12" 378 599 388 accc <br /> CO LL <br /> J <br /> Hood 2 3 Duct 12" 524 609 547 O Q U_. <br /> Total 1280 1731 1347 105% J 0_ 01 <br /> Lt <br /> OY Z <br /> 00 <br /> d <br /> V ~ <br /> W <br /> it-Y <br />