Laserfiche WebLink
INDIVIDUAL- TANK/LINE/LEAK DETECTOR TES IREPORT NDE <br /> NDE ENVIRONMENTAL CORPORATION „ <br /> TEST DATE: September 7, 1995 WORK ORDER NUMBER: 964592 <br /> CLIENT: SHELL PRODUCTS COMPANY SITE: SHELL 204-7524-4107 <br /> TANK WFORMATION <br /> Tank ID: 1 Bottom to top fill in inches: 144.5 <br /> Product: PREMIUM Bottom to grade fill in inches: 152.0 <br /> Capacity in gallons: 11,627 Fill pipe length in inches: 53.5 <br /> Diameter in inches: 91.00 Fill pipe diameter in inches: 4.0 <br /> Length in inches: 418 Stage I vapor recovery: DUAL <br /> Material: DBL. WALL Stage II vapor recovery: BALANCE <br /> Tank: NO <br /> Manifolded Vent: NO <br /> V/R: NO <br /> COMMENTS <br /> TANK TEST RESULTS LEAK DETECTOR RESULTS <br /> Test method: New/passed Failed/replaced <br /> Psi at tank bottom: detector detector <br /> Fluid level in inches: Test method: PTA <br /> UFT/OFT: Make: vAPoRLEss <br /> Fluid volume in gallons: Model: LD2000 <br /> Water level in inches: S/N: 35114 <br /> Test time: Open time in sec: 4.00 <br /> Number of thermisters: <br /> Specific gravity: Holding psi: 12 <br /> Resiliency cc: 250 <br /> Water table depth in inches: Test leak rate mVmin: 189.0 <br /> Determined by (method): Metering psi: 10 <br /> Leak rate in gph: Calib. leak in gph: 3.00 <br /> RESULT: RESULT: PASS <br /> COMMENTS COMMENTS <br /> RONAN ELECTRONIC LINE SENSOR. <br /> ULLAGE TEST RESULTS UNE TEST RESULTS <br /> Test method: <br /> Test time: Material: DWg=gERG <br /> Ullage volume: Diameter(in): 2.0 <br /> Length (ft): 50.0 <br /> Ullage pressure: Test psi: 50 <br /> RESULT: Bleedback cc: 35 <br /> DATA FOR UTS-4T ONLY: Test time (min): 30 <br /> Test 1:start time: 11:00 <br /> Time of test 1: finish Psi: 48 <br /> Temperature: vol change cc: 10 <br /> Flow rate (cfh): Test 2:start time: 11:10 <br /> Time of test 2: finish psi: 50 <br /> vol change cc: 0 <br /> Temperature: Test 3:start time: 11:20 <br /> Flow rate (cfh): finish psi: 50 <br /> Time of test 3: vol change cc: 0 <br /> Temperature: Final gph: 0.005 <br /> Flow rate (cfh): RESULT: PASS <br /> Test type: PTK-88 <br /> COMMENTS Pump type: PRESSURE Pump make: RED JACKET <br /> COMMENTS <br /> 8906 WALL STREET SUITE 306,AUSTIN,TEXAS 78754 5121 719-4633 <br />