Laserfiche WebLink
SWRCB,January 2002 Page of <br /> 5. SECONDARY PIPE TESTING <br /> Test Method Developed By: X Piping Manufacturer Industry Standard Professional Engineer <br /> Other(Spec) <br /> Test Method Used: X Pressure Vacuum Hydrostatic <br /> Other(Spec) <br /> Test Equipment Used:Pressure Gauges in Psi/Nitrogen Equipment Resolution: 1/10-15 Psi <br /> Piping Run#1 Piping Run#2 Piping Run#3 Piping Run# <br /> Piping Material: Fiberglass Fiberglass Fiberglass <br /> Piping Manufacturer: Smith Smith Smith <br /> Piping Diameter: 3" 3" 3" <br /> Length of Piping Run: Approx. 50' Approx. 50' Approx.50' OL --- <br /> Product Stored: Super 91 Regular 87 Diesel <br /> Method and location of Test hose at Test hose at Test hose at <br /> piping-run isolation: UDC#1&2 UDC#1&2 UDC#1&2 JUN 2 6 2015 <br /> Wait time between applying 15 Minutes 15 Minutes 15 Minutes <br /> pressure and startin test: �- <br /> Test Start Time: 11:10 12:00 11:30 -' ri_�n�nnoTe�r_sn <br /> Initial Reading(R,): 3 Psi 3 Psi 3 Psi <br /> Test End Time: 12:10 1:00 12:30 <br /> Final Reading(RF): 3 Psi 3 Psi 3 Psi <br /> Test Duration: 1 Hour 1 Hour 1 Hour <br /> Change in Reading(RF-R,): 0 Psi 0 Psi 0 Psi <br /> Pass/Fail Threshold or No detectable loss No detectable loss No detectable loss <br /> Criteria: <br /> Test Result: Pass Pass Pass <br /> Comments—(include information on repairs made prior to testing, and recommended follow-up for failed tests) <br /> Replaced old Blue Line Test Boots on Regular 87 and Diesel Secondary Pipe at Piping Sumps prior to testing. <br />