Laserfiche WebLink
DISPENSER SHUTDOWN MAPPING VERIFICATION TEST <br /> Dispenser fueling point numbers FP: 3 FP: 4 <br /> Test Result Y/N <br /> Dispenser was shutdown? Y <br /> Fuel was unable to be dispensed from fueling points associated with the dispenser? Y <br /> Dispenser was re-enabled? Y <br /> Fuel can be dispensed from fueling points associated with the dispenser? Y <br /> VAPOR FLOW METER V/L CHECK <br /> Vapor flow meter serial number 0842208 <br /> Dispenser fueling point numbers FP: 3 FP: 4 <br /> Low grade V/L result#1 1.07 1.12 <br /> ISD V/L value#1 1.08 1.15 <br /> Difference between V/L result#I and ISD V/L value#I (V/L–ISD V/L) .01 .03 <br /> Pass/Fail(Pass=difference within±0.15), if fail continue PASS PASS <br /> Low grade V/L result#2 <br /> Low grade V/L result#3 <br /> Average of 3 V/L results <br /> ISD V/L value#2 <br /> ISD V/L value#3 <br /> Average of 3 ISD V/L results JUN 2 6 2015 <br /> Difference between Average V/L and Average ISD V/L values hilanc in AM.— <br /> Pass/Fail(Pass=difference within±0.15) 4 4r_OIr - <br /> I declare, under penalty of perjury under the laws of the state of California that based on information and belief formed <br /> after reasonable inquiry, the statements and information provided in the document are true, accurate, and complete. <br /> Signature of Technician: �' ``' "" Date: 5/28/15 <br /> Vey. 1.'_ 08.W;'()8 <br />