Wednesday, June 02, 2004 11:40 AM Art Gomez 510-494-1596 <br /> p.17 <br /> i i ti s Hydrostatic Monitoring <br /> Part I: General The probe shall detect and report a change in liquid <br /> 1.0 The tank manufacturer shall supply a continuously mon- level either above(high-alarm point)or below(low-alarm <br /> itored hydrostatic head pressure leak detection systempoint) the neutral level established during the initial <br /> The system shall be designed by the manufacturer to filling and subsequent maintenance of the system. <br /> detect a leak in either the primary tank or the secondary The probe shall not operate by inducing an electrical <br /> tank in either a wet or dry excavation, current into the liquid medium that is being monitored. <br /> The system shall include: a monitoring fluid in the The sensing range represents a built-in allowance for <br /> interstice of the double-wall tank, a reservoir mounted pressure and thermal variation. Until the liquid level <br /> on top of the tank to provide a medium for monitoring, exceeds the allowable variation, the probe shall not <br /> and an electronic monitoring system to sound an send a signal to the monitor unit. <br /> audible and visual alarm when the liquid level of the The probe shall be capable of being mounted in the <br /> reservoir rises or falls to predetermined alarm points. reservoir in a manner that allows adjustment of location. <br /> Part II: Standards The probe must be able to be mounted so that normal <br /> fluctuation of the liquid level does not interfere with the <br /> 2.0 The double-wall tank with a brine-filled interstice shall be normal operation of the probe. <br /> listed by Underwriters Laboratories (UL).The electronic The probe shall be capable of operating at a distance of <br /> monitoring system used to monitor the liquid reservoir 500'from the control panel. <br /> and the attached collar riser shall also be listed by UL for 4.2 Attached Collar Riser Probe <br /> intrinsic safety in a hazardous location. (if applicable and shown on the drawing) <br /> All equipment shall be installed in accordance with the The probe shall be constructed of a material that is <br /> manufacturer's instructions and all applicable federal, suitable for prolonged, complete immersion in any of <br /> state and local laws and regulations. the fluids listed in Underwriters Laboratories(UL) <br /> Part III: Requirements for Standard for Safety 1316,Table 14.I,all columns. <br /> Liquid-Filled Double-Wall Tank The probe shall detect the presence of liquid in the riser <br /> 3.0 The interstice of the double-wall tank shall be factory- when the liquid level has risen to a maximum of one <br /> filled with a monitoring fluid.The reservoir shall be inch above the bottom of the probe, as located in its <br /> constructed of fiberglass and mounted directly to the permanent mounting position.The permanent mount- <br /> top <br /> ounttop of the tank. The reservoir shall be fitted with one ing position is determined by the installer at the time of <br /> 4" NPT fitting for installation of the electronic-reservoir installation. <br /> probe. The reservoir must remain vented at all times. The probe shall be capable of being mounted in the <br /> Part IV: Requirements for riser in a manner that allows adjustment of location. <br /> The probe shall be able to be mounted so that an <br /> Electronic Monitoring System increase in the liquid level does not interfere with the <br /> 4.0 The Controller normal operation of the probe. <br /> The panel shall receive the signal from the reservoir The probe-mounting assembly supplied and installed by <br /> and/or attached collar riser and provide for the contractors shall provide protection for the probe from <br /> following indications: the operational activities that may take place within the <br /> 1. System normal riser. <br /> 2. System fault(The"fault"indication must not be the The probe shall be capable of operating at a distance of <br /> same as the"alarm" indication.) <br /> 500'from the control panel. <br /> 3. Systern leak alarm 4.3 Operating Parameters: <br /> Also, a system test switch indicating the system is Temperature: 0°F to 150° F <br /> functional shall be provided. Voltage: 110 or 220 VAC, SO/60 Hz <br /> Al alarms shall be both audible and visible. Part V: Performance <br /> The unit shall be able to be reset. 5.0 The continuous hydrostatic monitoring system, <br /> The control panel shall provide indication of which tank including the electronics and the probes, shall be <br /> is in the alarm condition, if more than one tank is being capable of detecting and alarming when the liquid level <br /> monitored. in the tank reservoir rises or drops beyond the allowable <br /> The control panel shall be capable of monitoring up to variation. <br /> eight probe points. Part VI: Materials <br /> The system shall provide intrinsic safety at the probe 6.0 The materials used in the monitoring system shall be <br /> locations. corrosion-resistant to the liquid used to fill the interstice. <br /> 4.1 Reservoir Probe Part VII: Installation <br /> The probe shall be constructed of a material which is 7.0 The monitoring system shall be installed in accordance <br /> suitable for prolonged, complete immersion in the with the manufacturer's Installation Manual and <br /> monitoring liquid. Operating Guidelines, and all applicable federal, state <br /> The monitoring liquid may be: salt brine (30% CaCI in and local laws and regulations. <br /> water. <br />