Laserfiche WebLink
Monitoring System Certification �+ <br /> JUS f► 0 2017 <br /> D. Results of Testing/Servicing <br /> 'l�NV1RQN(�1r�tTuL <br /> Software Version Installed: 329.01 DEPARTMENT <br /> Complete the following checklist: <br /> ® Yes ❑ No* Is the audible alarm operational? <br /> ® Yes ❑ No* Is the visual alarm operational? <br /> ® Yes ❑ No* Were all sensors visually inspected,functionally tested,and confirmed operational? <br /> ® Yes ❑ No* Were all sensors installed at lowest point of secondary containment and positioned so that other equipment will <br /> not interfere with their proper operation? <br /> ❑ Yes ❑ No* If alarms are relayed to a remote monitoring station, is all communications equipment (e.g., modem) <br /> ® N/A operational? <br /> ® Yes ❑ No* For pressurized piping systems, does the turbine automatically shut down if the piping secondary containment <br /> ❑ N/A monitoring system detects a leak, fails to operate,or is electrically disconnected? If yes: which sensors initiate <br /> positive shut-down? (Check all that apply) ®Sump/Trench Sensors; ®Dispenser Containment Sensors. <br /> Did you confirm positive shut-down due to leaks and sensor failure/disconnection? ®Yes; ❑No. <br /> ® Yes ❑ No* For tank systems that utilize the monitoring system as the primary tank overfill warning device (i.e., no <br /> ❑ N/A mechanical overfill prevention valve is installed); is the overfill warning alarm visible and audible at the tank <br /> fill point(s)and operating properly? If so,at what percent of tank capacity does the alarm trigger? 90% <br /> ® Yes* ❑ No Was any monitoring equipment replaced? If yes, identify specific sensors,probes,or other equipment replaced <br /> and list the manufacturer name and model for all replacement parts in Section E,below. <br /> ® Ycs* ❑ No Was liquid found inside any secondary containment systems designed as dry systems? (Check all that apply) <br /> ®Product; ❑Water. If yes,describe causes in Section E,below. <br /> ® Yes ❑ No* Was monitoring system set-up reviewed to ensure proper settings?Attach set up reports,if applicable <br /> ® Yes ❑ No* Is all monitoring equipment operational per manufacturer's specifications? <br /> *In Section E below,describe how and when these deficiencies were or will be corrected. <br /> E. Comments: Note upon our arrival we opened regular STP sump lid and found fuel in the containment sump, <br /> 313 removed all liquid and entered STP sump could not find any source of leakage at any parts of the fueling system inside <br /> piping sump. Recommend re-inspection in thirty days to complete investigation. Fuel may have been from maintenance <br /> work. <br /> l o S <br /> ►� c � l P�� <br /> Page 2 of 3 <br />