Laserfiche WebLink
REI` ,zWED <br /> Mechanical / Electronic Leak Detector Test X17 <br /> +1=NTAL <br /> jARTMENT <br /> Site: Test Company <br /> West Valley Auto Service Pinnacle Fuel Compliance <br /> Chevron P.O. Box 32849 <br /> 2515 W.Grant Line Road San Jose, CA 95152 <br /> Tracy (408)206-9840 <br /> Test Information <br /> 1 2 3 4 <br /> Product Unleaded Super 'Diesel <br /> Manufacturer V/R V/R V/R <br /> Model PLLD PLLD PLLD <br /> Full Operating Pressure (psi) 36 38 28 <br /> Trip Time (sec) 6 7 6 <br /> F/E Holding Pressure (psi) 23 24 21 <br /> Test Leak Rate (ml/min)(gph) 190 190 190 <br /> PASS or FAIL PASS I PASS I PASS <br /> This form certifies that the annual line leak detector tests were performed at the above referenced facility <br /> according to the equipment manufacturers procedures and limitations and the results as listed are to my <br /> knowledge true and correct.The mechanical/electronic line leak detector test pass/fail is determined <br /> using a low flow rate threshold trip rate of 3 gph at 10psi. <br /> Tester: Aneil Chand Date: 6/28/2017 Q <br /> L� <br /> Signature: �� -- _ic# 90-1262 PINNACLE <br /> Mechanical/Electronic Leak Detector Test <br />