Laserfiche WebLink
San Joaquin County <br /> Environmental Health Department <br /> 1868 East Hazelton Avenue, Stockton, California 95205-6232 <br /> Telephone:(209)468-3420 Fax:(209)468-3433 Web:www.sigov.org/ehd <br /> Underground Storage Tank Program Inspection Report <br /> Facility Name: Facility Address: Date: <br /> WEST VALLEY AUTO SERVICE LLC 2615 W GRANT LINE RD. TRACY June 23, 2017 <br /> UST System Observations <br /> 323 HSC 25283.5(a) Unburied below grade UST system failed to meet exemption status =V R =COS <br /> 324 CCR 2717.1(g) Tampered with red tag =V ❑R ❑COS <br /> 325 CCR 2717.1(f) Deposited petroleum into a red tagged UST V ❑R ❑COS <br /> 326 HSC 25299(a)(9) Tampered with or disabled leak detection devices or alarms V _R COS <br /> 327 CCR 2631.1 UST system not compatible with the substance stored V Ei R COS <br /> 328 HSC 25298 Failed to comply with temporary closure requirements E:V ❑R ❑COS <br /> 329 HSC 25298 Failed to comply with permanent closure requirements _V R ❑COS <br /> 330 CCR 2636(f)(6) Failure to meet all requirements in lieu of a line leak detector for emergency generator tank system =V R COS <br /> Single-Walled Non-Pressurized Piping <br /> 401 CCR 2636(a)(3) Suction piping not properly sloped or incorrectly located check valve V R COS <br /> 402 CCR 2643(d) Daily monitoring of suction pipe(pre-Jan 1984)not performed =V =R COS <br /> 403 CCR 2643(d) Triennial 0.1 gph line test for conventional suction piping not performed(pre-January 1984) ❑V ❑R i:COS <br /> 404 CCR 2643(e) Biennial 0.1 gph test for gravity piping not performed(pre-January 1984) =V ❑R ❑COS <br /> Other Violations <br /> 2010 See below Unlisted Administration/Documentation violation V _:R COS <br /> 2030 See below Unlisted Operations/Maintenance violation ❑V ❑R n COS <br /> 2060 See below Unlisted Design/Construction violation =V -R ❑COS <br /> SUMMARY OF VIOLATIONS <br /> (CLASS 1,CLASS II,or MINOR-Notice to Comply) <br /> Item# Remarks <br /> 108 CCR 2637(f), 2638(e) Failed to notify the EHD 48 hours prior to conducting testing. <br /> Annual monitoring system certification, leak detector testing, and spill container testing were performed on March 1, <br /> 2017 without providing notification to the EHD at least 48 hours in advance. Notification shall be provided to the <br /> CUPA at least 48 hours in advance of testing. The EHD will not accept these results and testing must be <br /> rescheduled with a 48-hour notification. Testing was last performed on March 2016 and was due by March 2017. <br /> Immediately schedule these tests and provide 48 hours notification to the EHD. <br /> This is a minor violation. <br /> Overall Inspection Comments: <br /> Complete and submit a copy of the Return to Compliance Certification form to the EHD with a statement <br /> documenting the corrective actions that have been or will be taken for each violation, and any supporting <br /> paperwork, by July 23, 2017. <br /> Monitoring certification performed on March 1, 2017 is not being accepted by the EHD. A 48 hour notice was not <br /> provided to the EHD for that inspection and an inspector could not witness the testing because of it. A <br /> monitoring certification must be rescheduled and the EHD provided with a 48 hour notice. The EHD inspection <br /> will be charged at the hourly rate of the department at the time of the inspection. <br /> FA0014623 PRO521537 SCO01 06/23/2017 <br /> EHD 23-01 Rev.09/22/16 Page 3 of 4 Underground Storage Tank Program OIR <br />