Laserfiche WebLink
AUG 4 2015 <br />ENVIRONMENTAL <br />amec <br />I-JC61-U r1CQf%0T4A1:A1- foster <br />wheeler <br />Hydrostatic and Seismic Analysis Tank Name/marking: 1,000 Gal. <br />Waste Oil Tank <br />Overhead view: <br />See Attachment 1 <br />(Include all measurements. Does not need to be to scale) <br />Cross sectional (lateral) view: <br />See Attachment 1 <br />(Include all measurements. Does not need to be to scale) <br />Please provide a drawing of the seismic/hydrostatic anchorings used and their <br />spatial relationship to the tank. <br />At a minimum provide the following: <br />Calculation of the seismic load of the tank: <br />6.88 kips (ASCE 7-10) (Attachment 3) <br />Calculation of overturning moment of tank <br />192.51 k -in (ASCE 7-10) (Attachment 3) <br />Safety Factor: 3.13 (ASCE 7-10) <br />Demonstration that the resisting moment is greater than the overturn moment: <br />Safety Factor = (resisting moment/overturning moment) = >> 2 <br />Amec Foster Wheeler Environment & Infrastructure, Inc. 1,000 Gal. Waste Oil Tank <br />