Laserfiche WebLink
Hydrostatic and Seismic Analysis <br /> Please see Appendix "D" for calculations. The tank is not anchored <br /> to the concrete floor in the storage room. <br /> Discrepancies/Non compliant issues: None <br /> Used Coolant Storage Tank Assessment Page <br /> Tank Name/marking: UL # 489775 <br /> Tank age: 5 years : j� <br /> Remaining service life: Indefinite <br /> Ancillary Equipment: <br /> Suction Hose and fittings: 10 years <br /> Pneumatic Diaphragm Pump: 5 Years <br /> Copper Tubing: 35 years <br /> Tank Construction: <br /> Shape: Rectangular, Double Wall Construction <br /> Orientation: Horizontal, Rectangular, Double Wall Construction <br /> Location (above/below ground): Above Ground <br /> Material of construction: ASTM A-36 Carbon Steel <br /> " � <br /> Thickness and method used to determine: 0.1196" (11 gauge) as <br /> determined with a: Panametrics Model 360L Plus Ultrasonic Gage <br /> Lining material & thickness (if applicable): Epoxy, Thickness N/A <br /> Corrosion Protection equipment: <br /> Exterior corrosion protection is provided by a coat of epoxy paint <br /> applied over a sealing primer. <br /> Structural support: Tank is supported by a 10" thick reinforced concrete <br /> floor. <br /> 8 <br />