Laserfiche WebLink
SJCHHWCF <br />Seismic/Anchoring findings: The tank as <br />containment area in which it is located are a <br />seismically sound. <br />Initials: <br />Hazo,JouS Waste Oil Tank <br />operated and the <br />cored and are <br />Leak Test: Tank was in service at the time of inspection. No leaks were found, <br />the interstice is dry. <br />The tank is built to the UL 142 standard. The tank wall thickness exceeds <br />the minimum tank wall thickness of 2.36 mm. <br />Integrity testing findings: Bas don the above noted integrity test and the <br />results obtained from that test, tank has sufficient integrity for its intended <br />use. Initials: <br />Tank Drawing: <br />Strandberg Associates 348 Concord Dr Menlo Park, CA 94025 g <br />rwaterguv@rwaterguy.com (866) 388 0404 or (650) 329-8918 <br />SJC HHWC Waste Oil Secondary Containment Retrofit <br />Secondary Containment Treys <br />Tray <br />secondary containment <br />4'0x2"H <br />Trey M'x20"x4°H 24 Hour Leak Check by dalty Inspection <br />Note: Trough and secontlary Front View Facing Northwest <br />Containment Tray . <br />Tank Dimensions <br />11Px46"x56"High <br />Strandberg Associates 348 Concord Dr Menlo Park, CA 94025 g <br />rwaterguv@rwaterguy.com (866) 388 0404 or (650) 329-8918 <br />