Laserfiche WebLink
SJCHHWCF <br />Hazardous Waste Oil Tank <br />Seismic/Anchoring findings: The tank as designed nd operated and the <br />containment area in which it is located are adequate nchored and are <br />-seismically sound. Initials: <br />Leak Test: Tank was in service at the time of inspection. No leaks were found, <br />the interstice is dry. <br />The tank is built to the UL 142 standard. The tank wall thickness exceeds <br />the minimum tank wall thickness of 2.36 mm. <br />Integrity testing findings: Based on the <br />results obtained from that test, the tank h) <br />use. Initials: <br />Tank Drawing: <br />d integrity test and the <br />integrity for its intended <br />EIV E <br />SEP 0 4 2015 1... <br />Strandberg Associates 348 Concord Dr Menlo Park, CA 94025 8 <br />twaterguv(d).rwaterguV.com (866) 388 0404 or (650) 329-8918 <br />SJC HHWC Waste Oil Sewndary Containment Retrofit <br />9 .d.ry ConitimmeM Tray. <br />Tray <br />SewMary Conlelnment <br />m rH <br />TR Wxn'xeH 24HowLdk Cl C by aeTy Mspeamn <br />We: Trough aM 5erondary Front Vlew Fa W HO ryvt <br />Cordalnrrmt Trey <br />Twk Oimanelone: <br />111' x 48"x 55' High <br />Strandberg Associates 348 Concord Dr Menlo Park, CA 94025 8 <br />twaterguv(d).rwaterguV.com (866) 388 0404 or (650) 329-8918 <br />