Laserfiche WebLink
SJCHH Waste Antifreeze Tank <br />RECEIVED <br />SEP 04 2015 <br />Seismic/Anchoring findings: The tankas desi ed and operated and th&�4'Tu <br />containment area in which it is located are adeq tely anchored and are <br />seismically sound. Initials: <br />Leak Test: Tank was in service at the time of inspection. No leaks were found, <br />the interstice is dry. <br />The tank is built to the UL 142 standard. The tank wall thickness exceeds <br />the minimum tank wall thickness of 2.36 mm. <br />Integrity testing findings: Based on the above noted integrity test and the <br />results obtained from that test, the tanas sufficient integrity for its intended <br />use. Initials: l� <br />Tank Drawing: <br />SJC HHWC Waste Antifreeze secondary Containment Retrofit <br />Secondary Containment Treys <br />Z Tray]a"x28'x4'H <br />Note: Trough and secondary <br />Containment Tray . <br />24 Hour Leek Check by daily imeecbm <br />Front View Faring No(afwest <br />Tank Dimensions: <br />80" x 48'x58" High <br />Strandberg Associates 348 Concord Dr Menlo Park, CA 94025 <br />rwaterguvioi)rwaterguv.com (866) 388 0404 or (650) 329-8918 <br />OTlACNJT <br />Tray <br />.I,— <br />SecondaryContainment <br />4'DxYH <br />Z Tray]a"x28'x4'H <br />Note: Trough and secondary <br />Containment Tray . <br />24 Hour Leek Check by daily imeecbm <br />Front View Faring No(afwest <br />Tank Dimensions: <br />80" x 48'x58" High <br />Strandberg Associates 348 Concord Dr Menlo Park, CA 94025 <br />rwaterguvioi)rwaterguv.com (866) 388 0404 or (650) 329-8918 <br />OTlACNJT <br />