Laserfiche WebLink
SJCHHWCF Hazardous Waste Oil Tank <br />sel[smtcrAncnoring tmamgs: I ne tanK as aeslgnea na operatea ana <br />containment area in which it is located are adequatenchored and are <br />seismically sound. Initials: <br />Leak Test: Tank was in service at the time of inspection. No leaks were found, <br />the interstice is dry. <br />The tank is built to the UL 142 standard. The tank wall thickness exceeds <br />the minimum tank wall thickness of 2.36 mm. <br />Integrity testing findings: Based on the above noted integrity test and the <br />results obtained from that test, the tank hfisufficient integrity for its intended <br />use. Initials: <br />Tank Drawing: <br />ECEIVEL <br />SEP 0 3 2015 <br />ENVIRONMENTAL <br />I-t�p,T.14 t'SFPAPTAAcKIT <br />Strandberg Associates 348 Concord Dr Menlo Park, CA 94025 8 <br />rwaterguy(a).rwaterguy.com (866) 388 0404 or (650) 329-8918 <br />SJC HHWC Waste Oil Secondary Containment Retrofit <br />SecotMary Containment Trays <br />Tray <br />Sewntlary Containment <br />}"CxYH <br />Tray 3a'x0 x0"H V Hour Leak Check Ey dmly Nspeolion <br />Note: Trough and Secondary Front View Facing Northwest <br />Containment Tray. <br />Tank Dimensions: <br />111"x4 'x58 -High <br />Strandberg Associates 348 Concord Dr Menlo Park, CA 94025 8 <br />rwaterguy(a).rwaterguy.com (866) 388 0404 or (650) 329-8918 <br />