Laserfiche WebLink
Documentation of Corrective Actions <br /> RICompany <br /> Northwest Pipe San Joaquin County-Environmental Health Department <br /> Aboveground Petroleum Storage Act Inspection Report(02/10/2020) <br /> Pending corrections as per Cesar Ruvalcaba <br /> RequirementsSPCC Plan •nshore Facilities (excluding production <br /> 706 CFR 112.8(c)(2) Failed to provide and maintain adequate secondary containment <br /> The emergency generator was observed with insufficient secondary containment. There was no evident <br /> secondary containment for the belly tank of the generator. All bulk storage tanks must be provided with a <br /> secondary means of containment for the entire capacity of the tank and sufficient freeboard to contain <br /> precipitation. <br /> Corrective Action: <br /> Immediately provide sufficient secondary containment for this and all other tanks at this facility. <br /> A proper containment method for the emergency generator fuel (belly) tank has been identified, and is <br /> described the discharge or drainage control section;the new containment system is also mentioned in SPCC <br /> plan. <br /> Northwest Pipe Company hereby commits to custom fabricate containment with a capacity of-248 gallons, <br /> enough to contain the entire capacity of the 80 gallon belly tank plus sufficient freeboard to contain <br /> precipitation. <br /> NWP has fabricated 2CT as described above. <br /> I ' <br /> 1 I <br /> I � <br /> I , <br /> II <br /> f <br /> 0/ r <br /> '' 1117 <br /> t <br /> /4 <br /> Page 1 of 1 <br />