Laserfiche WebLink
Tracer Research Corporation <br /> 1 <br /> C)ERT1 FE CA 11 UN <br /> Job Number 140104 <br /> ' Date 85/22/92 <br /> Location Roush & Ready Island <br /> NSC <br /> Stockton, CA <br /> TANK# _ I'ItODIJLT SIZElgall _ _ TRACER LEAK STATUS <br /> Tank l Unleaded 4.000 DA Pass <br /> Tank 3 Unleaded 4,000 114B2 Pass <br /> Tracer Research Corporation certifies that the tank and pipe systems listed in the <br /> above table have been tested by means of Tracer Tight@, which meets the criteria set forth <br /> ' in NFPA 329 for a precision leak test According to EPA standard test procedures for <br /> evaluating leak detection methods the Tracer TightO method IS capable of detecting leaks <br /> of 0 05 gallons per hour with a Probability of Detection (PD) of U 97 and Probability of <br /> ' False Alarm (Pt A) oft} illy <br /> Submitted by <br /> Marty Fl k <br /> Tracer Research Corporation <br /> ' Testers State License Number 93- 1"273 <br /> ' The following, c.i itei is are used for the classification of leakage based on the presence or <br /> absence of tracer <br /> ' PASS EALL <br /> Criteria Criteria. <br /> ' No tracei deteett d tracer detected <br /> 1 <br /> - 3 - <br />