My WebLink
|
Help
|
About
|
Sign Out
Home
Browse
Search
WORK PLANS
Environmental Health - Public
>
EHD Program Facility Records by Street Name
>
K
>
KETTLEMAN
>
920
>
1600 - Food Program
>
PR0160119
>
WORK PLANS
Metadata
Thumbnails
Annotations
Entry Properties
Last modified
4/29/2020 10:55:20 AM
Creation date
4/8/2020 1:17:31 PM
Metadata
Fields
Template:
EHD - Public
ProgramCode
1600 - Food Program
File Section
WORK PLANS
RECORD_ID
PR0160119
PE
1626
FACILITY_ID
FA0000569
FACILITY_NAME
LUU'S CHICKEN BOWL #4
STREET_NUMBER
920
Direction
W
STREET_NAME
KETTLEMAN
STREET_TYPE
LN
City
LODI
Zip
95240
APN
06004007
CURRENT_STATUS
01
SITE_LOCATION
920 W KETTLEMAN LN
P_LOCATION
02
P_DISTRICT
004
QC Status
Approved
Scanner
JCastaneda
Tags
EHD - Public
There are no annotations on this page.
Document management portal powered by Laserfiche WebLink 9 © 1998-2015
Laserfiche.
All rights reserved.
/
35
PDF
Print
Pages to print
Enter page numbers and/or page ranges separated by commas. For example, 1,3,5-12.
After downloading, print the document using a PDF reader (e.g. Adobe Reader).
View images
View plain text
5. Performance <br /> A. 3MTm Fire Barrier Duct Wrap 615+ has been tested in C. Thermal Conductivity <br /> accordance with the following: <br /> Btar - in. W <br /> ASTM E 2336 Standard Test Methods for Fire Resistive Grease Duct Temp. <br /> hr-ft2-'F nr'-K <br /> Enclosure Systems <br /> 500°F 0.48 0.07 <br /> ASTM E 119 Standard Test Methods for Fire Tests of Building Construction (260°C) <br /> and Materials 1 000'F <br /> ASTM E 814 Standard Test Method for Fire Tests of Through-Penetration (553737°.C)0) 0.97 0.14 <br /> Fire Stops <br /> ASTM E 136 Standard Test Method for Behavior of Material in a Vertical 1500°F 1.57 0.23 <br /> Tube Furnace at 750°C (1382°F) (815°C) <br /> ASTM C 518 Standard Test Method for Steady-State Thermal Transmission 1800°F 1.98 0.29 <br /> Properties by Means of the Heat Flow Meter Apparatus (982°C) <br /> ASTM C 1338 Standard Test Method for Determining Fungi Resistance of 2000°F <br /> Insulation Materials and Facings (1093°C) 2.23 0.33 <br /> ASTM E 84 Standard Test Method for Surface Burning Characteristics of <br /> Building Materials <br /> ISO 6944-85 Fire Resistance Tests-Ventilation Ducts D. Linear Shrinkage <br /> 24 Hr @ 2012°F (1000°C): 1.2% <br /> B. Surface Burning Characteristics (ASTM E 84, ULC/CAN S-102) E. R-Value <br /> Single layer of 3MTm Fire Barrier <br /> Flame Spread Smoke Developed Duct Wrap 615+ at 77°F (25°C): <br /> Foil Encapsulated Blanket <25 <50 6 38 F-f- - h, <br /> Brit <br /> F. Design Listings <br /> Fire Resistive Third-Party Testing Services <br /> Rating I Enclosure System Design Listing Description <br /> Grease Duct Listings-ASTM E 2336 <br /> 2 layers of 3MTm Fire Barrier Intertek 3MU/FRD 120-18 48 x 48 in. <br /> 1 and 2 Hour Duct Wrap 615+, minimum Rectangular <br /> 3 in. (76 mm) perimeter and <br /> longitudinal overlaps Intertek 3MU/FRD 120-19 48 in. Round <br /> Ventilation Duct Listings- ISO 6944 <br /> 1 layer of 3MTm Fire Barrier Intertek 3MU/FRD 120-15 24 x 85 in. <br /> 1 and 2 Hour Duct Wrap 615+, minimum Underwriters Laboratories HNLJ.V-27 Rectangular <br /> 3 in. (76 mm) perimeter and <br /> longitudinal overlaps Intertek 3MU/FRD 120-04 40 in. Round <br /> G. Codes and Standards <br /> 3MTm Fire Barrier Duct Wrap 3MTm Fire Barrier Duct Wrap 615+ installed per ISO 6944 tested Design <br /> 615+ installed per ASTM E 2336 Listings can be utilized to meet the requirements of the following codes: <br /> tested Design Listings meets the <br /> requirements of the following codes: NFPA 92A Standard for Smoke-Control System Utilizing Barriers and <br /> Pressure Differences, 2006 Edition-Section 6.6.2 <br /> NFPA 96, 2008 Edition NFPA 92B Standard for Smoke Management Systems in Malls, Atria, <br /> 2006/2009 International and Large Spaces, 2005 Edition -Section 7.5.2 <br /> Mechanical Code NFPA 1010 Life Safety Code°, 2006 Edition-Section(s) 8.6.7, 18.7.7 <br /> International Mechanical Code°, 2006 Edition -Section 513.10.2 <br /> International Building Code', 2006 Edition-Section 909.10.2 <br /> These are only partial lists for design listings and code requirements. For the latest code and approval information <br /> go to www.3M.com/firestop or speak to your authorized 3M distributor or sales representative at (800) 328-1687. <br /> 2 <br />
The URL can be used to link to this page
Your browser does not support the video tag.