Laserfiche WebLink
(D) Provide positive shut-off of flow to the tank so that none of the fittings located on the <br /> top of the tank are exposed to product due to overfilling. <br /> The station had selected option C "Provide positive shut-off of flow to the tank when the tank is <br /> filled to no more than 95%of capacity"as the form of overfill prevention for this facility. <br /> VIOLATION: The overfill prevention system was manually overridden and was not <br /> functioning in accordance with CCR 2635(b)(2)(C). <br /> CCR 2665. Spill and Overfill Prevention Equipment Upgrade Requirements. By December 22, <br /> 1998, all underground storage tank system shall be retrofitted with an overfill prevention system <br /> and spill container which meet the requirements of section 2635(b). <br /> VIOLATION: The overfill prevention system was manually overridden and was not <br /> functioning in accordance with CCR 2635(b)(2)(C). <br /> V. ADDITIONAL ATTACHMENTS <br /> Attachment 1 -Copy of inspection report conducted on 10/5/04 <br /> Attachment 2 -Pictures of violation <br /> Attachment 3—Copy of Boyett Petroleum invoice <br /> Dennis Catanyag,REH Date \O o <br /> Registered Environme ealth�Sp i <br />