Laserfiche WebLink
the controller be bypassed (as long as some surge voltage protection is still provided) to allow the <br /> motors to use the line frequency directly rather than a recreated waveform <br /> 4 2 2 3 Remote Pump Restart Because of the frequent power disruptions (see Sec 4 1 7 1, <br /> Retuning Problems or Issues), modifying the control of the extraction wells, to include an remote VFD <br /> pump re-start option should be considered Although it is recognized that in some cases the cause of the <br /> pump shutdown should be confirmed, if the operator has clear indication that power fluctuations <br /> occurred at the time the pumps went down, then an inspection is not necessary and the remote restart <br /> capability could be used This would potentially save 100 person-hours per year (25 outages times 4 <br /> hours per restart) <br /> 4 2 2 4 Conduit Protection Seasonal cattle grazing is allowed in the site area Conduit <br /> to the extraction well heads have been severed by cattle rubbing up against the well heads <br /> Reinforcing the attachment of the conduit to the well head should be considered to make the well <br /> heads `cattle-proof <br /> 4 2 3 Operating Parameter Changes <br /> 4 2 3 1 Air Stripper Operation Currently two blowers, with a third on standby, are <br /> providing air to the two air strippers The air strippers were designed to reduce TCE levels from <br /> 250 ppb to 0 78 ppb The number of gas transfer units (N) is a measure of the capacity to <br /> remove contaminants by air stripping Given information about the contaminant (including <br /> concentration), packing material, and the air and water flow rates both the required and actual <br /> (operational) number of gas transfer units can be estimated The higher the N, the more ability <br /> the stripper has to remove contaminants As currently configured, the air strippers are estimated <br /> to offer a 5 7 N capacity The current level of TCE in the influent is about 20 ppb The Ns <br /> needed to reduce the TCE levels from 20 ppb to 0 78 ppb are estimated to be 3 4, less than what <br /> is currently available Thus, the strippers have excess capacity to remove TCE Reducing the <br /> depth of the packing would result in lower energy consumption by the blowers and estimated <br /> electricity savings of about $300 per month The cost of removing packing would have to be <br /> recovered within a relatively short period of time to justify the change The cost (mostly labor) of <br /> removing the packing was not estimated Reducing the air input to the strippers should also be <br /> evaluated If the air rate is reduced by half with, the input concentration of TCE at 20 ppb, and <br /> the required effluent concentration remaining at 0 78 ppb, an estimated capacity of only 0 8 Ns <br /> are needed Performance curves should be obtained from the manufacturer to determine if the <br /> blower will operate efficiently and correctly at the reduced rate This would also result in lower <br /> energy consumption Using a combination of both reduced airflow and reduced packing should <br /> also be evaluated If both the airflow rate and the packing height can be reduced, a single blower <br /> may M dble to pio-vide sullil,lent air too booth all Jtrippels at Mr, 1VWer required pres,�?lLre T11e NT <br /> values are based on a flow rate through each air stripper of 13,425 cfrn (from the AE design <br /> analysis) and 4-inch of water pressure drop across the packing (observed during the site visit) If <br /> the actual values are different, the above figures need to be adjusted accordingly Finally, if at a <br /> later time the influent concentration approaches the concentration that can be reinfected, it may <br /> be possible to strip only a portion of the water and recombine it with the other portion for <br /> reinfection <br /> 06/07/99 <br /> Page 10 of 14 <br />