- HOOD ELECTRICAL PLAN NOTES <br />DIVISION 16 - GENERAL ELECTRICAL - <br />GENERAL <br />1 INSTALL ALL ELECTRICAL IN THIS WORK PER LATEST NEC AND CITY OF STOCKTON BUILDING DEPT. <br />REQUIREMENTS. FLEXIBLE CONDUIT MAY BE USED BUT MUST CARRY GROUND WIRE TO BOX. SWITCH <br />LIGHTING AS INDICATED ON DRAWINGS. ALL CIRCUITS SHALL BE MARKED TO INDICATE AREAS SERVED. <br />PROVIDE ADDITIONAL CIRCUITS AS REQUIRED BY OTHER TRADES. GENERAL ELECTRICAL MAYBE RUN IN <br />FLEXIBLE METAL CONDUIT, MC OR EMT. SETSCREW FITTINGS ON EMT. MC CABLE TO USED IN CONCEALED <br />WALL OR CEILING. INSTALL ALL FIXTURES PER MFG REQ. USE ONLY APPROVED AND LISTED EQUIPMENT. <br />CONDUCTORS SHALL BE COPPER CONDUCTORS TYPE THWNITHHN. USE CONNECTORS APPROVED FOR <br />RELATED WIRE SIZE. THE USE OF STRANDED OR SOLID APPROVED. USE STRANDED FOR SIZES #8 OR <br />LARGER <br />3. ALL WORK SHALL CONFORM TO THE CEC 2013 EDITION AND TO THE APPLICABLE REQUIREMENTS OF LOCAL, <br />STATE, AND FEDERAL CODE(S) AND/OR AGENCIES HAVING JURISDICTION; AND SHALL TAKE PRECEDENCE <br />OVER WORK SHOWN. ANY DISCREPANCIES SHALL BE BROUGHT TO THE ATTENTIONOF THE DESIGNER <br />PRIOR TO THE INSTALLATION OF WORK. <br />4 ELECTRICAL CONTRACTOR SHALL VERIFY DIAGRAMMATIC LAYOUT OF ELECTRICAL WORK WITH OWNER <br />PRIOR TO INSTALLATION. <br />5• SEE ELECTRICAL SYMBOLS, VERIFY ALL SYMBOLS AND CONDITIONS AS REQUIRED PRIOR TO INSTALLATION. <br />JOB CONDITIONS <br />ELECTRICAL DRAWINGS: THE ELECTRICAL DRAWINGS, AS CONTAINED, ARE ESSENTIALLY <br />6. DIAGRAMMATIC AND ALTHOUGH THE SIZE AND LOCATION OF EQUIPMENT ARE SHOWN TO SCALE <br />WHEREVER POSSIBLE CONTRACTOR SHALL MAKE USE OF ALL DATA AND VERIFY THIS <br />INFORMATION AT THE BUILDING SITE. THE DATES INDICATED ON THE DRAWINGS AND IN THE <br />JOB CONDITIONS AND DECISIONS OF THE DESIGNER WILL GOVERN EXACT LOCATIONS, <br />DISTANCES, LEVELS, AND OTHER CONDITIONS. <br />OPERATION: <br />7 THE SYSTEM SHALL BE COMPLETE AND FULLY FUNCTIONING TO THE SATISFACTION OF THE DESIGNER AND <br />THE OWNER. INSTALL ALL CIRCUITS, J-BOXFS, WIRING DISCONNECTS AND ANY OTHER EQUIPMENT NEEDED <br />TO PROVIDE ELECTRICAL SERVICE FOR SIGNAGE. <br />g. DRAWINGS - <br />THE LAYOUT OF LIGHT FIXTURES ARE TO BE DIVIDED IN THE ROOM AS SHOWN ON THE PLANS. ANY Questions <br />ABOUT LAYOUT SHOULD BE DIRECTED TO THE ENGINEER. UPON COMPLETION OF THE INSTALLATION, <br />FURNISH A SET OF 'RECORD' (AS -BUILT) DRAWINGS TO THE DESIGNER CLEARLY MARKED WITH THE <br />CHANGES AUTHORIZED DURING CONSTRUCTION, CUTTING NOTCHING DRILLING CONTRACTOR SHALL BE <br />RESPONSIBLE FOR ALL WORK HEREIN INCLUDING CUTTING, BORING, NOTCHING, FURRING AND DRILLING AS <br />NECESSARY TO COMPLETE THIS PROJECT. "NOTE: NO CUTTING, BORING, NOTCHING, FURRING AND <br />DRILLING OF TRUSS OR OTHER STRUCTURAL MEMBERS WILL BE ALLOWED. CONTRACTOR SHALL <br />COORDINATE WITH OTHER TRADES TO ALLOW FOR GROUP RUNS AND ELIMINATE ANY OVERLAPPING OR <br />OBSTRUCTION. <br />9. <br />WORKING CLEARANCES <br />WORKING CLEARANCE REQUIREMENTS FOR ALL ELECTRICAL EQUIPMENT INCLUDING DISCONNECTS WILL BE <br />MAINTAINED AS PER CEC 2010 ARITCLE 110.26 <br />10 COMPLETION OF WORK AND TEST <br />THE ENTIRE ELECTRICAL SYSTEM SHALL BE FREE FROM ANY SHORT CIRCUITS, AND IMPROPER GROUNDS. <br />DEMONSTRATE WITH THE OWNER AND DESIGNER THAT THE ENTIRE INSTALLATION IS COMPLETE AND IN <br />PROPER OPERATING CONDITION. <br />i <br />1. Dur;ng i ­of -,nal operation, both exhaust -fan <br />ant MaKeup a in on position <br />20 When Ansel Sys tem is acUva+ed, make up <br />air hooch lights c:nd all elect{ ice devices VV '11 <br />the hood Will be cuterrc-Jtically -1.ur-ned Off. <br />H 0 0 D E X I A lil/ I- I_ A U 0 ISI A C �! Y B E <br />LJRN!ED 0, all elec;tri!;;a e guipmen-T, dev1ce S, <br />receptacles, lighting; etc. to be loca Led within <br />and under i.he hood footprint. <br />All receptacics (net,,, and existing) in all <br />l <br />kitchen food prep areas siia'll be GFC <br />prote(-ted. <br />FastlWraW"k' XL <br />AJ Them I Cemmics <br />C4mmer ia[ Kitchen Grease Duct Enclosure System <br />Air Ventilation Duct Ertctosure Systettt <br />f res:op art rated Rocr and wail assemblies FastWrap XL as UL <br />%IaGsilted and is port Df Lit.'s Lis;itig and Foilow-Up Service <br />Program to ensure the •;c-nilstent g%iahty essential to the criti- <br />cal nature of this fife -safety application.. <br />Product Features <br />• Zero clearance to ceni"vtibles at anY locaticn <br />Thin and Lightweight at 1-1)2 inch think, 6 pc.f density <br />• Contours easily to complex duct designs <br />• <br />Buttjointson Inside layer • Aa'rd labor, space, 3rd rAater,a: <br />• Fully rail encapsulated for fast and clean installation <br />Completely inorganic and non-aornbustiiaie <br />Contains 2C@0°F rated I bees For added safety margin <br />Contains na loin temperature rninerai or glass fibers <br />Wide variety of through penetration systems <br />Resistant to mold growth <br />• Extensive Listings and dat1114d installahon irstn:cticn.s <br />Oftrereel in 60 and 100 square fact roils <br />Available in 48 inch widths for less joints and installation <br />labor <br />Reference Standard Standard No. <br />Pe-rformance <br />Prcduot Data & Instaflatiort Guide <br />pass <br />t. Froiluct Description <br />Pass <br />6Cerarritls' new FlreMaster ;:MtVlrir '9L is the <br />Pass <br />tta;en"t and lightest flexible wrap rnaterial.availaiaie tat pass- <br />$ <br />es the AS -T64 E 2335 test:standard required by the 2000 IMC <br />Pass <br />and NFPA Lad for reduced ctearaneo enclosure matonals used <br />Pass <br />io provide I or 2 hour fire rating for kitchen exhaust ducts. <br />_ <br />f'astWrap XL is alas VL Ctassiried and Labe:ed per 130 0944 <br />5�v <br />a9 ar alternative to a t or 2 hour rated e-nciosure for air vent!- <br />lation ducts The FaslWrap XL core blan$iet is manufactomd <br />4 2s :h <br />using Thermal Ceramics patented Suyerwooil� fiber. a 2400'F <br />Res'str: <br />rated, non-comt)u%tita!e, slkar:rte-earth 34:1icata wool with low. <br />Pass <br />biopersistence. FastWrap XL is the product of extensive <br />Pass <br />rosoarch and developrnont resuhing In break•thrcugh improva- <br />. N...,x <br />rnents in stgodicart tnhancerrnerts <br />in thermal properties beneficial to Eire protection apptleatiOns- <br />PastWrap XL when u*eti in t:vmbin,atlon with an approved <br />q;rostop sealant provides an o"ective through penetration <br />A. Performance 5peciCnations <br />f res:op art rated Rocr and wail assemblies FastWrap XL as UL <br />%IaGsilted and is port Df Lit.'s Lis;itig and Foilow-Up Service <br />Program to ensure the •;c-nilstent g%iahty essential to the criti- <br />cal nature of this fife -safety application.. <br />Product Features <br />• Zero clearance to ceni"vtibles at anY locaticn <br />Thin and Lightweight at 1-1)2 inch think, 6 pc.f density <br />• Contours easily to complex duct designs <br />• <br />Buttjointson Inside layer • Aa'rd labor, space, 3rd rAater,a: <br />• Fully rail encapsulated for fast and clean installation <br />Completely inorganic and non-aornbustiiaie <br />Contains 2C@0°F rated I bees For added safety margin <br />Contains na loin temperature rninerai or glass fibers <br />Wide variety of through penetration systems <br />Resistant to mold growth <br />• Extensive Listings and dat1114d installahon irstn:cticn.s <br />Oftrereel in 60 and 100 square fact roils <br />Available in 48 inch widths for less joints and installation <br />labor <br />Reference Standard Standard No. <br />Pe-rformance <br />Creast Duct Enclosure System ASTM i;.Z:30 <br />pass <br />2,ect .• t8 l - .`on- A:T1.1 r— .t.. <br />G'OiY.lrStllvtl'ty <br />Pass <br />Ressance AaTM E,i'a <br />iwail'i <br />Pass <br />Esct:a*. `6.3 - Durab,lny 7+s; AwTM 'MA <br />Pass <br />Seen t5-< - "aural Fire Test ASTM c'.'3 6 <br />Pass <br />rire Enii ^i <br />-duck ASTMc' 4E`I� <br />Pass <br />Surface Burning [IiaiaLOFfI5t1Gs <br />F dint Spead ii¢%'blar:hetl ASTM E54 <br />5�v <br />_rrroke Develoce4 A3TM EEA <br />T-hemal es!stance iR-v«tue ASTtS .'fi 10 <br />7D'F) <br />4 2s :h <br />Maid Grow* 17556 -95% A,TM D9328 <br />humidity) <br />Res'str: <br />Air Ventilation must Enelasure 1 :� 11 4 <br />Pass <br />Grease timet Enclosure System JUL t97,S' <br />Pass <br />nrr'M.•r .wt -I rY�. ni. r., ,k err .-M1-.s x•YNr-,. �.'�ernu <br />. N...,x <br />2. Applications <br />• Applied in 2 layers to provide i or hour fire protection to <br />grease ducts exhausting Type t hoods per 2006 WC. Nr FA S LtstiegsiMuitding Cndk Reports <br />0 and 2006 IAPMO. UMC <br />• Applied in t Payer as an akematwe to a T or 2 hour rated <br />sled uses <br />eri,60sure for air Ventilation oucis <br />3. Phy5imai Charaoteristias <br />Product <br />;Unrt Sixe <br />UnitlI YVf.7 <br />Can- Ctrt. <br />Fs56� ry Xi <br />li '1-1:C^ N 24, X �5' <br />1 37 $1L�. <br />Fast"Nran Y1. <br />Rall t. 1''^ a �i v 24' <br />1 7 Ebs. <br />Fasr4'nno X� Cotiar <br />Rall I-tf=' s d' , `b' <br />4 37 ° lbs. <br />Caor <br />White btankel rrilh stwi'nil enaapstAafca <br />Li <br />Agency <br />11511119 <br />`.'i5$ Duct f',nV1'J'iu re .o}fS:iiT: i�STC <br />Ieara�l�e} - AC I � -, ;F.3T)A E2:tir2s <br />AREA LOAD 112 <br />v.-jra5*Duct Enc fas.fe::ySxm?Zerc <br />uk,JxJ trej -AF7,M E2?3'' <br />IGC -E,' <br />G3:R22!,; <br />Throuin?eretaacmEireS;opSy-ter^-ASTM1j,L <br />cc.4; L <br />5•seF!gWii <br />VenS3tan Duct Eerdosum System - ISO 6P.4 <br />[JL <br />J' 3 <br />91411 n!A CToi ItITI IDAI 11tH TC.viii <br />STRUCTURAL CALCULATION HOOD 'I <br />TRIBUTARY AREA: 114 (4 HANGING ANGLES, 1 AT EACH <br />CORNER) <br />HOOD LOAD: 449 LBS TOTAL <br />280 LBS (TOTAL HOOD WEIGHT) / 4 (TRIBUTARY AREA) = 112 LBS PER THREADED ROD <br />112 LBS < 60,000 LBS (THREADED ROD TENSILE STRENGTH CAPACITY) = OK <br />0 <br />TRIBUTARY <br />AREA LOAD 112 <br />LBS PER BOLT <br />4 <br />0 <br />�— MANUFACTURERS HOOD <br />HANGING ANGLES. SEE HOOD <br />DRAWINGS, SHEET H1 <br />HOOD WEIGHT <br />DISTRIBUTION DIAGRAM <br />STRUCTURAL CALCULATION HOOD 2 <br />TRIBUTARY AREA: 114 (4 HANGING ANGLES, 1 AT EACH <br />CORNER) <br />HOOD LOAD: 564 LBS TOTAL <br />564 LBS (TOTAL HOOD WEIGHT) 14 (TRIBUTARY AREA) = 112 LBS PER THREADED ROD <br />141 LBS < 60,000 LBS (THREADED ROD TENSILE STRENGTH CAPACITY) = OK <br />0 <br />TRIBUTARY <br />AREA LOAD 141 <br />LBS PER BOLT <br />o <br />O <br />- HOOD DETAIL'S <br />SCALE: 1" = V-0" <br />MANUFACTURERS HOOD <br />HANGING ANGLES. SEE HOOD <br />DRAWINGS, SHEET H1 <br />-• — HOOD WEIGHT <br />DISTRIBUTION DIAGRAM <br />- (E) ENGINEERED <br />WOOD TRUSSES <br />(3) TOTAL DIAGONAL <br />STEEL L1 -112x1 -112x3116 <br />WELDED SOLID <br />FRAMES (1 EACH <br />SHORT END AND 1 <br />ACROSS FRONT OF <br />HOOD) <br />APEX <br />ARCHITECTURE <br />845 S. Commerce Street <br />Stockton, CA. 95206 <br />(209) 662-4874 <br />apexplanning@hotmail.com <br />Steven Anthony Torres II <br />Architect # C32553 <br />PROPERTY OWNER <br />Francisco Javier Llamas <br />CONTRACTOR <br />tbd <br />EL GRULLITO <br />RESTAURANT T.I. <br />STOCKTON <br />1687 N. Californian Street, Suite #3 <br />Stockton, CA. 95204 <br />HOOD DETAILS <br />AR <br />EIC# C 32553 <br />REN. 3-31 j9/s <br />�p � <br />fi c - <br />REV.# HATE tSSUED DESCRIPTION <br />APEX PROJECT 18-19 <br />DATE:10-14-2018 <br />All <br />DATE Copyright APEX <br />