Laserfiche WebLink
Triangle Environmental, Inc. <br /> T.E.I. SYSTEMS TANK, LINE AND LEAK DETECTOR TEST REPORT <br /> Facility: QUIKSTOP #00132 <br /> Tank #: 3 Work #: 460985 <br /> Product: Unleaded Premium Test Date: 8/ 2/99 <br /> NONE=: EMENEW <br /> Test Method: Test Method: R.J.FTA <br /> Capacity: Manufacturer: Vaporless <br /> Diameter(in): L/D Model: LD2000 <br /> Product Level(in): L/D Serial#: 65490 <br /> Liquid Volume(Gals): Line Drain Back(ml): 90 <br /> Liquid Percent(%): L/D Trip Time(sec): 2 <br /> Specific Gravity: Holding Pressure(psi): 24 <br /> Coef. of Expansion: Metering Pressure(psi): 18 <br /> Water On Tank(in): L/D Test Rate(gph): 1.6 <br /> Water In Tank(in): L/D Result: PASS <br /> Product Temp. (F): <br /> Head Pressure(psi): <br /> Test Start Time: <br /> Test Method: <br /> Test End Time: <br /> h : Pump Brand: <br /> Test Rate <br /> (gph): System Type: <br /> Test Result: N/A <br /> Line Pressure(psi): <br /> 10 Line Start Time: <br /> Test Method: ULLAGE Line End Time: <br /> UllageVolume(gals.): Line Start Level: <br /> Ullage Test Time: Line End Level: <br /> Ullage Vacuum(psi): Line Test Rate(gph): <br /> Ullage Result: N/A Line Test Result: N/A <br /> 2 <br />