Laserfiche WebLink
UNDER DISPESER CONTAINMENT C TESTING <br /> Test Method By: O Manufacturer • Industry Standard o Professional Engr o Other(see below) <br /> Test Method Uses: O Pressure O Vacuum • Hydrostatic o Other(see below) <br /> Measuring Equipment Used: INCON TS-STS (Electronic Sump Test System) <br /> Description Disp#1/2 Disp#3/4 Disp#5/6 Disp#7/8 <br /> UDC manufacturer Bravo Bravo Bravo Bravo <br /> UDC material FRP FRP FRP FRP <br /> UDC depth (inches) 30 30 30 30 <br /> Height from UDC bottom to highest <br /> piping penetration 11 8 12 10 <br /> Height from UDC bottom to lowest <br /> electrical penetration 4 Bottom 4 4 <br /> Condition of UDC prior to testing Dry Dry Dry Dry <br /> Portion of UDC tested Entire Entire Entire Entire <br /> Type of shut-down present Sensor Sensor Sensor Sensor <br /> Was sensor removed for testing? Yes Yes Yes Yes <br /> Was sensor properly replaced after testing? Yes Yes Yes Yes <br /> Depth of water level from UDC bottom (in.) 15 15 15 15 <br /> Wait time for water level to stabilize (hr:min) 0:10 0:15 0:15 0:10 <br /> Test start time 11:39 AM 10:22 AM 11:39 AM 10:22 AM <br /> Initial Probe Reading 3.3657 6.1519 4.2829 5.7726 <br /> Test end time 11:55 AM 10:37 AM 11:55 AM 10:37 AM <br /> Final Probe Reading 3.3651 6.1518 4.2827 5.7727 <br /> Test duration (hr:min) 0:16 0:15 0:.16 0:15 <br /> Change in water level (t 0.0000 inches) -0.0006 -0.0001 -0.0002 0.0001 <br /> Pass/Fail threshold 40.0020 inches/;Hr.) 0.0020 0.0020 0.0020 0.0020 <br /> TEST RESULT PASS PASS PASS PASS <br /> Comments: <br /> © 2006 Walton Engineering,Inc. <br />