Laserfiche WebLink
LINE LEAIDETECTOR (LLD) TE* REPORT <br />PR 2 7 2015 <br />TEST DATE: April 22, 2015 <br />A1. FACILITY <br />1 <br />A2. OWNER <br />Name <br />Quik Stop Market #132 <br />San Joaquin County Environmental Health <br />Name <br />Quik Stop Markets, Inc. 1417- A' -?J rnDDpDT'gAC?%jT <br />Address <br />3555 W. Hammer Lane, Stockton, CA 95219 <br />1868 E. Hazelton Avenue, Stockton, CA 95202 <br />Address <br />4567 Enterprise Street, Fremont, CA 94538 <br />Phone # <br />510-657-8500 <br />April 14, 2015 <br />Phone # <br />510-657-8500 <br />Contact <br />Roger Batra <br />Cindy Vo <br />Contact <br />Debbie Markovich <br />A3. C U P A <br />1 <br />Product contained <br />A4. TESTING CONTRACTOR <br />Name <br />San Joaquin County Environmental Health <br />VMI 99LD-2000 <br />Name <br />Walton Engineering, Inc. <br />Address <br />1868 E. Hazelton Avenue, Stockton, CA 95202 <br />Resiliency (ml) <br />Address <br />P.O. Box 1025, W. Sacramento, CA 95691 <br />Notified <br />April 14, 2015 <br />26 <br />Lic # <br />617238 A, B, Haz <br />Inspector <br />Cindy Vo <br />Full Flow Opening time (seconds) <br />Contact <br />Veronica Freitas <br />Phone # <br />209-468-8257 <br />Phone # <br />916-373-1166 <br />I. LINE LEAK DETECTOR TEST RESULTS <br />Test Equipment Used: Vaporless VMI LDT-890 <br />Tank number <br />1 <br />Product contained <br />Gasoline -87 <br />MLLD <br />Leak Detector Type <br />Leak detector make/model <br />VMI 99LD-2000 <br />Serial number <br />7031208 <br />Functional Element Holding (psi) <br />26 <br />Resiliency (ml) <br />55 <br />Test leak rate (gph) <br />3.00 <br />_ <br />Pump pressure (psi) <br />26 <br />Metering pressure (psi) <br />Pressure Restriction Reduction (psi) <br />13 <br />13 <br />30 _ <br />5 <br />PASS <br />Length of Restriction Test (seconds) <br />Full Flow Opening time (seconds) <br />TEST RESULT <br />Tank number <br />Product contained <br />Leak Detector Type <br />Leak detector make/model <br />Serial number <br />Functional Element Holding (psi) <br />Resiliency (ml) <br />Test leak rate (gph) <br />Pump pressure (psi) <br />Metering pressure (psi) <br />Pressure Restriction Reduction (psi) <br />Length of Restriction Test (seconds) <br />Full Flow Opening time (seconds) <br />TEST RESULT <br />J. COMMENTS: <br />2 <br />Gasoline -89 <br />MLLD <br />VMI 99LD-2000 <br />7031338 <br />26 <br />55 <br />3.00 <br />26 <br />18 <br />8 <br />30 <br />3 <br />PASS <br />3 _ <br />Gasoline -91 <br />MLLD <br />FE Petro STP -MLD <br />1080379 <br />26 <br />65 <br />3.00 _ <br />26 <br />9 <br />17 <br />30 <br />PASS <br />Signature: <br />�TJ y WALTON <br />ENGINEERING, INC. <br />Technician: Thomas Steiger A31060/8156310 Date: April 22, 2015 <br />