SEPTEMBER 27, 2002 <br /> • ARCO FAC 6335 <br /> PETCON 4855 SOUTH ROUTE 99 /ARCH ROAD <br /> TECHNOLOGIES STOCKTON, CA <br /> INC. <br /> SCOPE OF WORK <br /> TO REPAIR THESE FAILED COMPONENTS <br /> 91 SECONDARY LINES <br /> 87, 91 TURBINE SUMPS <br /> 87, 89, 91 FILL SUMPS <br /> 87 (south), 89, 91 SPILL BUCKETS <br /> 1/2, 3/4, 5/6, 7/8, 9/10, 11/12, 13/14, 15/16, 17/18 DISPENSER PANS <br /> 14118 S.Inglewood Avenue <br /> Hawthorne,CA 90250 1. PERFORM HELIUM TEST TO LOCATE AND PINPOINT LEAK ON <br /> SECONDARY LINE. <br /> T 310 679 9991 a. TIGHTEN CLAMPS, RESEAT BOOTS. <br /> F 310 679 9994 b. IF NEEDED, EXCAVATE PORTION OF TANK SLAB AND <br /> REPAIR PIPING PER MANUFACTURER'S <br /> RECOMMENDATIONS. <br /> c. IF NEEDED, REPLACE PENETRATION BOOTS ON <br /> ptimail@petcontech.com DISPENSERS. <br /> www,petcontech.com 2. REPAIR LEAKS IN TURBINE / FILL SUMPS <br /> a. TIGHTEN CLAMPS, RESEAT BOOTS <br /> b. SEAL SUMPS COLLARS WITH FIBERGLASS AND RESIN. <br /> c. INSTALL SSI WEAVER PENETRATION FITTINGS WHERE <br /> PIPING / CONDUIT PASSES THROUGH SUMP WALL. <br /> 3. REPAIR SPILL BUCKETS <br /> a. CLEAN / REPLACE DRAIN VALVES <br /> b. CLEAN / REPLACE GASKETS <br /> c. IF NEEDED, REPLACE SPILL BUCKETS TO MATCH <br /> EXISTING. <br /> 4. REPAIR UDCs <br /> a. TIGHTEN BOOTS <br /> b. REPLACE BOOTS IF TORN <br /> c. INSTALL SSI WEAVER PENETRATION FITTINGS WHERE <br /> PIPING / CONDUIT PASSES THROUGH DISPENSER PAN <br /> WALL. <br /> d. IF NEEDED, EXCAVATE PORTION OF TANK SLAB TO <br /> TIGHTEN / REPLACE UNDERGROUND PENETRATION <br /> BOOTS <br />