i <br /> • SWRCB..lanuar% 2002 Page %= . <br /> 9. SPILL/OVERFILL CONTAINMENT BOXES <br /> Facility is Not Equipped With Spill/Overfill Containment Boxes: <br /> Spill/Overfill Containment Boxes are Present, but were Not Tested: <br /> Test Method Developed By: F� Spill Bucket Manufacturer ❑x Industry Standard ❑ Professional Engineer <br /> ❑ Other(Specify) <br /> I est Method Used: ❑ Pressure El Vacuum ❑x Hydrostatic <br /> Other(Specili•) <br /> I C,t I.yuilm int I tiCd: Equipment Resolu on: <br /> Spill Box# -- -JL Spill Box# 2-MID Spill Box# 3-PRE Spill Box# <br /> Bucket Diameter: 12 12 12 <br /> Bucket Depth: 14 14 14 <br /> Wait time between applying <br /> pressure/vacuum/water and 1 MIN 1 MIN 1 MIN <br /> starting test: <br /> Test Start Time: 1:4 0 1:40 1:40 <br /> Initial Reading(RI ): 11 11 11 <br /> Test End Time: 2:40 2:40 2:40 <br /> Final Reading(RF ): 8 11 11 <br /> Test Duration: 1 HR 1 HR 1 HR <br /> Change in Reading(R F-RI ) 3 0 0 <br /> Pass/Fail Threshold or VISIBLE LOSS VISIBLE LOSS VISIBLE LOSS <br /> Criteria: <br /> Test Result: E Pass a Fail M Pass E Fail El Pass 1:1 Fail 1:1 Pass 1:1 Fail <br /> Comments - (include inf6rination on repairs made prior to testing, and recommended follow-up for failed tests) <br /> 87 SPILL LEAKING OUT OF THE SIDE OF BUCKET. CALLED IN FOR REPAIRS ECS# 6680131. BUCKET <br /> IS IN OPW SUMP. <br />