Laserfiche WebLink
SCOPE OF WORK <br /> Installation of EVR Phase II Upgrade <br /> Existing ARCO Retail Fueling Facility <br /> 1711 E. Yosemite,Manteca,California 95336 <br /> ARCO Fac.No. 6020/Our Job No. 13455 <br /> • Retrofit existing dispensers with new EVR Phase 11 equipment pei CARB Exec. Order <br /> VR-202-F <br /> • Install one new Veeder-Root ISD pressure sensor at dispenser ne est the tanks <br /> • Install one new Veeder-Root ISD vapor flow meter at each dispenser <br /> • Install the Clean Air Separator(CAS) on concrete pad with enclos are <br /> • Install bollards for Clean Air Separator(CAS)protection <br /> • Manifold existing gasoline vent risers and connect 1" vent line fro m Healy tank to vent <br /> stack manifold <br /> • Replace existing Veeder-Root monitoring panel,and install new eeder-Root TLS-35OR <br /> panel at the existing location. <br />