Laserfiche WebLink
Quality Tune-Up <br /> 1014 N EI Dorado Stret <br /> Stockton, CA 95202 <br /> TANK ASSESSMENT 480 GA USED OIL HOLDING AST <br /> Facility inspection by Qaniel K. Barber RCE California and Certified Steel Tank Institute Inspector. <br /> Inspection:July 18, 2011.1 <br /> Owner Contact: Gerald)Garduno, Shop Manager Quality Tune-Up (209) 547-9084 <br /> CONTAINMENT ASSESSMENT <br /> The double wall steel AST lays horizontally within in a concrete floor equipment maintenance shop. <br /> Adequate sizing for cor tained AST is provided by a secondary welded 10 gauge (.1345 IN) plate shell. <br /> There is adequate containment capacity for failure of the 480 GA primary "hazardous waste" containing <br /> waste oil AST. The concrete floor readily supports the subject waste oil AST. <br /> Attached to the rectangular"Lube Cube" ®AST is a highly visible GRACO pneumatic 1 IN transfer pump <br /> and piping. The shop's finished concrete floor and raised AST provides a Continuous Release Detection <br /> Method (CRDM)with visible indication of spillage prior to ground contact. <br /> Daily observations for visible signs of leakage are to be recorded by Quality Tune-Up staff in keeping <br /> with the Spill Prevention Control and Countermeasures Plan. <br /> Records are to maintai ed on site for 3 years. <br />