Laserfiche WebLink
SA I D 10 A Q, 6 I N Environmental Health Department <br /> NDE <br /> Underground Storage Tank Program Inspection Report <br /> Facility Name: Facility Address: Date: <br /> ARCO 06080 85 E LOUISE AVE, LATHROP January 29, 2018 <br /> SUMMARY OF VIOLATIONS <br /> (CLASS I,CLASS II,or MINOR-Notice to Comply) <br /> Item # Remarks <br /> 113 CCR 2638(4) Failed to submit monitoring system certification test report within 30 days. <br /> Annual monitoring system certification, leak detector testing, and spill container testing was performed on 2/1/2017 <br /> and a test report was submitted passed 30 days. A copy of the test report must be submitted within 30 days of the <br /> tests. Take all necessary precautions to ensure testing and submittal of test reports are performed in a timely <br /> manner. <br /> This is a minor violation. <br /> 206 CCR 2712 Failure to comply with UST operating permit conditions. <br /> The S11 Vacuum sensor was replaced on 1/11/2018 and a permit was not obtained from the EHD. Emergency <br /> repairs relating to UST system monitoring and release detection may be performed by a properly licensed, trained, <br /> and certified contractor pursuant to the EHUS policy and a permit obtained within one business day from the EHD. <br /> All other repairs must have a permit submitted to and approved by the EHD prior to beginning work. Immediately <br /> obtain a permit from the EHD for the replacement of the S11 Vacuum sensor. A"Failure to Obtain a Permit' penalty <br /> applies. <br /> This is a minor violation. <br /> 304 HSC 25290.1(d) Monitoring system not maintained to detect entry into secondary containment (after Jul 2004). <br /> The dispenser#3/4 208 sensor failed to activate an audible and visual alarm when tested to ensure continuous <br /> monitoring of the tank system. All monitoring equipment shall be maintained to activate an audible and visual alarm <br /> or stop the flow of product at the dispenser when it detects a leak. The sensor was replaced and retested during the <br /> inspection by the technician. A"UST Retrofit Verification with Inspector Already Onsite" form has been completed <br /> and provided to the operator and contractor. <br /> This was corrected on site. <br /> This is a repeat violation, Class II. <br /> 313 HSC 25290.1, 25290.2, 25291 Failure to construct, operate, and maintain primary containment as product-tight. <br /> Weepage was observed on the diesel pipe in the dispenser#4, indicating a leak in the primary piping. All primary <br /> containment for the UST system must be tight. Immediately have a properly licensed, trained, and certified <br /> contractor repair or replace the failed component under permit and inspection of the EHD. <br /> This is a repeat violation, Class II. <br /> FA0003635 PR0231656 SC001 01/29/2018 <br /> EHD 23-01 Rev.10/31/2017 Page 4 of 5 Underground Storage Tank Program OIR <br /> 1868 E. Hazelton Avenue I Stockton, California 952051 T 209 468-34201 F 209 464-0138 1 www.sjcehd.com <br />