Laserfiche WebLink
C-7 <br /> MAR Q 9 2017 <br /> I N ENVIRONMENTAL _ALTH <br /> Line Leak Detector Test Data Sheet <br /> DEPARTiOENT <br /> Station # Arco 6080 Date 2/1 2017 <br /> Address 85 E. Louise Avenue, Lathrop, CA <br /> Test Information <br /> 1 2 3 4 5 <br /> Product 87 91 Diesel <br /> Manufacturer VR VR VR <br /> Model 848480 848480 848480 <br /> Full Operating Pressure (psi) 35 47 32 <br /> Line Bleed Back (ml) NA NA NA <br /> Trip Time (sec) NA NA NA <br /> Metering Pressure (psi) NA NA NA <br /> F/E Holding Pressure (psi) 22 21 19 <br /> Test Leak Rate (ml/min)(gph) 189ml 189ml 189ml <br /> PASS or FAIL P P P <br /> Comments: <br /> This letter certifies that the annual leak detector tests were performed at the above referenced facility <br /> according to the equipment manufacturers procedures and limitations and the results as listed are to my <br /> knowledge true and correct. The mechanical leak test detector test pass/fail is determined using a low <br /> flow threshold trip rate of 3 gph at 10 PSI. <br /> Inspected By: Contractor Gettler-Ryan Inc. <br /> Technician Gilbert Garcia Lie# <br /> Signature <br />