Laserfiche WebLink
bp <br /> MAR 02 20� <br /> ENWHO1061�iIV`fiq� <br /> LJCn:TI.i l��r-n <br /> Line Leak Detector Test Data Sheet <br /> Station# 6080 Date 212 16 <br /> 20 <br /> Address 85 E Louise Ave <br /> Lathrop, CA <br /> Test Information <br /> 1 z 3 4 5 <br /> Product 87 91 DSL <br /> Manufacturer VR VR VR <br /> Model 848480 848480 848480 <br /> Full Operating Pressure 37 38 32 <br /> Line Bleed Back(ml) NA NA NA <br /> Trip Time(sec) NA NA NA <br /> Metering Pressure(psi) NA NA NA <br /> F/E Holding Pressure(psi) 25 21 31 <br /> Test Leak Rate(ml/min)(gph) 189m! 189MI 189ml <br /> PASS or FAIL P P P <br /> Comments: <br /> This letter certifies that the annual leak detector tests were performed at the above referenced facility <br /> according to the equipment manufacturers procedures and limitations and the results as listed are to my <br /> knowledge true and correct. The mechanical leak test detector test pass/fail is determined using a low <br /> flow threshold trip rate of 3 gph at 10 PSI. <br /> Inspected By: Contractor Gettler-Ryan Inc. <br /> Technician Tim Adams Lie# <br /> Signature <br />