Laserfiche WebLink
by <br /> Line Leak Detector Test Data Sheet <br /> Station # Arco 6080 Date 1/29/2018 20 <br /> Address 85 E Louise Ave. Lathrop, CA <br /> Test Information <br /> 1 2 3 4 5 <br /> Product 87 91 <br /> DSL <br /> Manufacturer VR VR VR <br /> Model 848480 848480 848480 <br /> Full Operating Pressure (psi) 35 47 32 <br /> Line Bleed Back(ml) NA NA NA <br /> Trip Time (sec) NA NA NA <br /> Metering Pressure (psi) NA NA NA <br /> F/E Holding Pressure(psi) 22 21 19 <br /> Test Leak Rate(ml/min)(gph) 18 9ML 18 9ML 189 ML <br /> PASS or FAIL PASS PASS PASS <br /> Comments: <br /> This letter certifies that the annual leak detector tests were performed at the above referenced facility <br /> according to the equipment manufacturers procedures and limitations and the results as listed are to my <br /> knowledge true and correct. The mechanical leak test detector test pass/fail is determined using a low <br /> flow threshold trip rate of 3 gph at 10 PSI. <br /> Inspected By: Contractor Gettler Ryan Inc <br /> Technician David Rouse Lic#B44848 <br /> Signature <br />