circumference seam in any 10 feet. Short joints between screen sections <br /> may be required. r <br /> 1. All joints of any stainless steel casing sections shall be closed by <br /> continuous welding. A welding sequence shall be followed which will <br /> avoid excessive distortion. All joints shall be welded watertight with a <br /> minimum 90% penetration. Welding shall be in accordance with <br /> applicable provisions of the latest edition of the American Welding <br /> Society publication, "Transmission Pipelines". <br /> 2. If plain end, beveled or butt-welded casing is used, no less than four <br /> straps, 114-inch thick and 1-112 inches wide shall be provided and used <br /> at each joint. If welding collars are used, no welding straps shall be <br /> required. Welding collars shall be the same material as the casing. <br /> 3. Dielectric couplings shall be used at all joints between dissimilar metals. <br /> H. Casing Guides: Centering guides shall be welded or attached in a an <br /> approved manner to the outside of conductor, screen and well casing <br /> sections to center the elements in the bore hole. Centering guides shall, at a <br /> minimum, consist of 2-inch-wide by 318-inch-thick steel, having a bearing <br /> area of at least 1-foot length at the casing/bore interface. Centering guides <br /> shall of the same material as the casing and/or screen, welded at both ends <br /> to the casing and screen and bent to form a guide at the required depth. <br /> Centering guides shall be sized to create a uniform annular space around the <br /> casing in the bore hole. <br /> ,a <br /> 1. On conductor casing, a minimum of ei ht centering guides shall be <br /> provided at each of the following locations: 4 feet from the bottom, <br /> 4 feet from the ground surface and in between at intervals of not over-40 <br /> feet. <br /> 2. On the screen, centering guides shall be provided at the top and bottom <br /> and in between at intervals of not over 40 feet. shall be provided <br /> 3. On the well casing, a minimum of fqr, centering guides p x <br /> at the following locations: 4 feet from the bottom of the well screen, <br /> 4 feet up from the bottom of the conductor casing, 4 feet below ground <br /> I;Vel, and in between at intervals of not over 40 feet. <br /> v <br /> 2.02 WATER <br /> h <br /> A. Water used in well construction and disinfection shall be potable water from a <br /> source approved by the Engineer. The City will issue a "no fee" water permit <br /> for the Contractor's use of a nearby fire hydrant. The Contractor or on the <br /> supply <br /> a City-approved backflow prevention device at the fire hydrant <br /> water truck. r—.- <br /> �t' <br /> 2.03 DRILLING FLUID <br /> A. A circulating fluid shall be maintained at all times during the drilling -Vf <br /> operations. No mud additive shall be used without demonstrated need. If an b <br /> additive is required to do a satisfactory job, it shall be an inorganic, non- <br /> Division III- 17 <br /> f <br />