Laserfiche WebLink
13. Results of Testing/Servicing <br /> Software Version Installed: 325.04 <br /> Complete the follo ing checklist: <br /> ®Yes ❑No* Is the audible alarm operational? <br /> ®Yes ❑ No* Is the visual alarm operational? <br /> ®Yes ❑ No* Were all sensors visually ins ected,functionally tested,and confirmed operational? <br /> ®Yes ❑ No* Were all sensors installed at lowest point of secondary containment and positioned so that other equipment will <br /> not interfere with then proper operation? <br /> ®Yes ❑ No* If alarms are relayed to a remote monitoring station, is all communications equipment (e.g. modem) <br /> ❑ N/A operational? <br /> ® Yes ❑ No* For pressurized piping systems, does the turbine automatically shut down if the piping secondary containment <br /> ❑ N/A monitoring system detects a leak, fails to operate,or is electrically disconnected? If yes:which sensors initiate <br /> positive shut-down? (Check all that apply) ®Sump/Trench Sensors;®Dispenser Containment Sensors. <br /> Did you confirm positive shut-down due to leaks and sensor failure/disconnection? ®Yes; ❑No. <br /> ® Yes ❑ No* For tank systems that utilize the monitoring system as the primary tank overfill warning device (i.e. no <br /> ❑N/A mechanical overfill prevention valve is installed), is the overfill warning alarm visible and audible at the tank j <br /> fillpoint(s)and operating properly? If so,at what percent of tank capacity does the alarm trigger? 90% <br /> ❑Yes* ® No Was any monitoring equipment replaced? If yes,identify specific sensors,probes,or other equipment replaced <br /> and list the manufacturer name and model for all replacement parts in Section E,below. <br /> ❑Yes* ® No Was liquid found inside any secondary containment systems designed as dry systems? (Check all that apply) <br /> ❑Product; ❑Water. If yes,describe causes in Section E,below. <br /> ®Yes ❑ No* Was monitoring system set-up reviewed to ensure proper settings?Attach set up reports,if applicable <br /> ®Yes ❑ No* I Is all monitoring equipment oerational per manufacturer's specifications? <br /> *In Section E below,describe how and when these deficiencies were or will be corrected. <br /> I <br /> E. Comments: <br /> Small amount of water in the 89 STP sump <br /> i <br /> Page 2 of 4 <br />