Laserfiche WebLink
Page L of <br /> 5. SECONDARY PIPE TESTING <br /> Test Method Developed By: p Piping Manufacturer ®Industry Standard ❑Professional Engineer <br /> ❑Other(Specify) _ <br /> Test Method Used: ®Pressure ❑ Vacuum ❑Hydrostatic <br /> [I Other(Specify) <br /> Test Equipment Used: DIAL GAUGE Equipment Resolution:0 to 15"psi <br /> Piping Run# g-7 Piping Run# g ef Piping Run# q Piping Run# <br /> Piping Material: Fiberglass Fiberglass Fiberglass Fiberglass <br /> Piping Manufacturer: S S y <br /> Piping Diameter: 3 3 ' <br /> Length of Piping Run: 5e-- <br /> Product Stored: <<� 7 G 4 9 C Y/ <br /> Method and location of _ <br /> piping-run isolation: <br /> Wait time between applying <br /> pressure/vacuum/waterand 15 Minutes 15 Minutes 15 Minutes 15 Minutes <br /> starting test: <br /> Test Start Time: y.'3 ° 3 �•`f <br /> Initial Reading(RD: 5 PSI 5 PSI 5 PSI 5 PSI <br /> Test End Time: /pa Yc7 /z,..-'L- <br /> Final Reading(RF): Jr PSI 5 PSI S PSI PSI <br /> Test Duration: 1 Hour 1 Hour 1 Hour 1 Hour <br /> Change in Reading(RF-Rl): S9' PSI PSI jo PSI PSI <br /> Pass/Fail Threshold or Zero Zero Zero Zero <br /> Criteria: <br /> Test Result: a Pass ❑Fail I ig Pass ❑Fail 9 ,Pass ❑ Fail ❑ Pass ❑Fail <br /> Comments—(include information on repairs inade prior to testing, and recommended follow;up for failed tests) <br /> Arco # 06080 <br /> 85 E. Louise Avenue <br /> Lathrop, CA 95330 <br /> N05115- SB 989 Testing <br />