Laserfiche WebLink
SNYDER INDUSTRIES INC. DATE 9/312010 <br /> TANK RESTRAINT CALCULATIONS-SEISMIC & WIND ANALYSIS BY TAM <br /> JOB# El 0-071 <br /> PROJECT NAME SNYDER INDUSTRIES INC, <br /> WIND ANCHORAGE DESIGN <br /> CABLE DESIGN 7X19 STAINLESS STEEL AIRCRAFT CABLE <br /> CABLE BREAK DESIGN <br /> ANCHOR DESIGN DIA. STRENGTI STRENGTH <br /> (IN) (LBS) (LBS) <br /> ANCHOR TYPE 3/4" HIM HIT-RE 500 SD 3/16 3,700 925 <br /> 1/4 6,400 1,600 <br /> 5/16 9,000 2,250 <br /> 3/8 12,000 3,000 <br /> 7/16 16,300 4,075 <br /> STAB. CABLE CABLE <br /> FORCE FORCE SIZE ANCHOR FORCES <br /> CONTAIN PRIMARY #of <br /> TANK TANK Cable Ph REQ'D <br /> MODEL MODEL# Sets (LBS) Pc(LBS) (IN) Rv(LRS) Rh (LBS) <br /> 100050ON 574000ON 246 381 3/16 340 419 <br /> DESIGN SUMMARY: <br /> ANCHOR TYPE: 3/4" Hiiti HIT-RE 500 SD ICC-ES#ESR-2322, 2500 psi concrete. <br /> PRIMARY TANK BOLTS CABLE <br /> CONTAIN PRIMARY <br /> TANK MODEL TANK CAP DIAM E(IN) <br /> IAM. <br /> # MODEL# (GAL) (FT) HT(FT) PLAN SPACE 7Hc(FT) <br /> 100050ON 574000ON 275 3.50 4.35 0 OK 3.50 3/16 <br /> Page 4 <br />