Laserfiche WebLink
wood. <br /> in an area where there is a chance of flooding 0.2% annually or once every 500 <br /> years, with water deeper than 1 foot. See Flood Zone Viewer map in Attachment <br /> 3. Hydrostatic Analysis in Attachment 3 indicates that the tank will not become <br /> buoyant, even if fully submerged in a 500 year flood. Similarly, sliding forces from <br /> the design earthquake are insufficient to cause the tank to move or to overturn. <br /> Seismic/Anchoring findings: The tank as designed and operated, and the containment <br /> area in which it is located are adequately anchored and meet minimum seismic s f <br /> standards. Initials: <br /> Leak Test 66265.192(k)(10): <br /> Brief description of leak test, including type of test used, and results of test: This <br /> tank was integrity tested based on the Steel Tank Institute's Standard SP001, <br /> "Standard for the Inspection of Aboveground Storage Tanks" (STI SP001) and <br /> recommendations from the manufacturer. This standard provides recommended <br /> integrity testing schedules based on risk to the environment, considering factors <br /> such as spill control, release detection methods, and storage capacity. Table 5.5, <br /> "Table of Inspection Schedules", of STI SP001 recommends tanks of this size <br /> and type undergo periodic, visual, documented inspections to assess general <br /> AST conditions. These inspections may be conducted by the AST owner and <br /> without suspending AST operations or removing the AST from service. Holt of <br /> California conducts these types of inspections on a daily basis. The tank <br /> inspector reviewed Holt of California inspection logs and conducted his own <br /> assessment based on the attached checklist. The tank was deemed to be in <br /> proper working order and the integrity sound. Sample inspection logs are located <br /> in Attachment 2. <br /> Integrity testing findings: Based on the above noted integrity test and the results <br /> obtained from that test, the tank has sufficient integrity for its intended use. <br /> Initials: <br /> Wood Environment & Infrastructure Solutions, Inc. 1,000 Gal. Waste Oil Tank <br />