<br /> <br />Wood Environment & Infrastructure Solutions, Inc. 275 Gal. Waste Antifreeze Tank <br />Hydrostatic and Seismic Analysis Tank Name/marking: 275 Gal. Waste <br />Antifreeze Tank <br /> <br />Overhead view: <br /> <br />See Attachment 3 manufacturer’s drawing. <br /> <br /> (Include all measurements. Does not need to be to scale) <br />Cross sectional (lateral) view: <br /> <br />See Attachment 3 manufacturer’s drawing. <br /> <br /> <br /> (Include all measurements. Does not need to be to scale) <br />Please provide a drawing of the seismic/hydrostatic anchorings used and their <br />spatial relationship to the tank. <br /> <br />Anchoring Assembly Description <br />The tank is seismically restrained using a SII tank seismic restraint system <br />recommended for SII 35 – 500 gallon dual containment tank (DCT) systems. The <br />anchor system is constructed from angle iron (3”x3”x1/4” thick) and 7X19 <br />stainless steel aircraft cable (1/4-inch diameter). Structural calculations for the <br />DCT system were prepared by Associated Design & Engineering, Inc. and are <br />presented in Attachment 3. <br /> <br />At a minimum provide the following: <br />Calculation of the seismic load of the tank: <br />0.63 kips (ASCE 7-16) (Attachment 3) <br /> <br />Calculation of overturning moment of tank <br />17.78 k-in (ASCE 7-16) (Attachment 3) <br />Safety Factor: 7.07 (ASCE 7-16) <br /> <br />Demonstration that the resisting moment is greater than the overturn moment: <br />Safety Factor = (resisting moment/overturning moment) = >> 2 <br />