Laserfiche WebLink
Gardner Trucking, Used Oil Tank, 22§CCR 66265.192, November 2019 <br /> 4.0 Inspection <br /> 4.1 Results: <br /> 4.1.1 Foundation: <br /> The Used Oil tank is sitting on a concrete foundation. No cracks, spalling or other <br /> deficiencies were found in the foundation. The tank is secured to the wall by any <br /> mechanical means and the seismic evaluation shows no risk of overturning or sliding. <br /> The foundation appears to be sufficient to maintain the full load of the tank based upon <br /> its many years of service at this location. <br /> 4.1.2 Containment: <br /> The Used Oil Tank is a double-walled aboveground tank with secondary containment <br /> capable of containing 100% of the contents and is intrinsically designed to prevent <br /> exposure to precipitation. The interstice was free of any waste. <br /> 4.1.3 Shell: <br /> The inner and outer shell are constructed of carbon steel of unknown specification, but <br /> assumed to be A36 commercial steel. It is a double walled horizontal rectangular design. <br /> The shell exterior was visually inspected and appears in satisfactory condition. The <br /> coating was inspected for disbonding, adhesion, deterioration, and discoloration(See <br /> Section 4.1.6). A visual inspection was conducted over the exterior shell including the <br /> shell external welds. No discrepancies were noted on the welds. The minimum design <br /> thickness requirements per UL-142 for the tank is 0.093". The UT inspection of the tank <br /> revealed no indications that the wall thickness has dropped below the design <br /> requirements listed in UL-142. Thickness measurements are listed in the engineering data <br /> in Appendix B. The Used Oil tank was labeled in accordance with NFPA 704. <br /> 4.1.4 Appurtenances: <br /> Inspected and evaluated each tank nozzle in accordance with STI SP-001. Evaluated all <br /> nozzles and reinforcement plates for leaks and corrosion. Both the primary tank and <br /> interstice are equipped with a Morrison Bros Fig 244 emergency vent. Every <br /> aboveground storage tank shall have emergency relief venting...that will relieve <br /> excessive internal pressure caused by an exposure to fire (NFPA 30 22.7.1.1. The Used <br /> Oil tank has a Kruger Sentry Gauge installed for the purpose of measuring the liquid <br /> level. The gauge was verified to be accurate during the inspection. The Used Oil tank has <br /> an auto shut off valve installed to help prevent overfills. This valve will turn off the air <br /> supplied by the compressor to the Husky 1050 pump. <br /> 4.1.5 Painting/Insulation: <br /> There are minimal areas of coating failure throughout the shell and roof of the tank. The <br /> corrosion is surface-oriented at this time. <br /> 4.1.6 Piping: <br /> The Used Oil Tank has a 1" carbon steel receipt piping system comprised of multiple <br /> elbows, couplers, and a double diaphragm pump. The piping travels up the ceiling to the <br /> center of the shop,regularly supported by uni-strut supports. The Graco Husky 1050 <br /> Diaphragm Pump is anchored to prevent movement. The installation date of the <br /> 5 <br />