My WebLink
|
Help
|
About
|
Sign Out
Home
Browse
Search
COMPLIANCE INFO_2020
Environmental Health - Public
>
EHD Program Facility Records by Street Name
>
A
>
ARMY
>
1624
>
2300 - Underground Storage Tank Program
>
PR0231014
>
COMPLIANCE INFO_2020
Metadata
Thumbnails
Annotations
Entry Properties
Last modified
7/10/2020 4:16:03 PM
Creation date
5/14/2020 4:20:48 PM
Metadata
Fields
Template:
EHD - Public
ProgramCode
2300 - Underground Storage Tank Program
File Section
COMPLIANCE INFO
FileName_PostFix
2020
RECORD_ID
PR0231014
PE
2361
FACILITY_ID
FA0003777
FACILITY_NAME
ARMY COURT
STREET_NUMBER
1624
STREET_NAME
ARMY
STREET_TYPE
CT
City
STOCKTON
Zip
95206
APN
16334002
CURRENT_STATUS
01
SITE_LOCATION
1624 ARMY CT
P_LOCATION
01
P_DISTRICT
001
QC Status
Approved
Scanner
SJGOV\gmartinez
Tags
EHD - Public
There are no annotations on this page.
Document management portal powered by Laserfiche WebLink 9 © 1998-2015
Laserfiche.
All rights reserved.
/
25
PDF
Print
Pages to print
Enter page numbers and/or page ranges separated by commas. For example, 1,3,5-12.
After downloading, print the document using a PDF reader (e.g. Adobe Reader).
View images
View plain text
A J OA U I Environmental Health Department <br /> COUNTY <br /> Underground Storage Tank Program Inspection Report <br /> Facility Name: Facility Address: Date: <br /> ARMY COURT 1 1624 ARMY CT, STOCKTON October 25, 2019 <br /> SUMMARY OF VIOLATIONS <br /> (CLASS I,CLASS II,or MINOR-Notice to Comply) <br /> Item# Remarks <br /> 205 CCR 2712(1), 2634(e) Failure to submit a current UST Response Plan and have it available onsite. <br /> OBSERVATION: An approved copy of the response plan was not available for inspection. <br /> REGULATION GUIDANCE: A copy of this plan shall be accessible on site at all times. <br /> CORRECTIVE ACTION: Immediately locate and retain a copy on site. <br /> This is a minor violation. <br /> 209 CCR 2716(a-e) Failure to conduct the designated UST operator visual inspection at least once every 30 days. <br /> The designated operator inspection was conducted on 06/18/2018 and the next report was conducted on <br /> 06/09/2019 one year late. The designated operator report shall be conducted within 30days of the previous <br /> inspections report. <br /> Ensure that all designed operator inspection reports are performed within the required time frame. <br /> This is a minor violation. <br /> 210 CCR 2716(f) DO monthly reports not maintained on site for 12 months or for 36 months (after October 1, 2018). <br /> Observation: The 2018 designated operator monthly inspection reports were not found on site. The most recent <br /> inspection report on site is 6/26/18. An alarm history dated 6/6/19 was observed on site but the inspection report <br /> was not found. <br /> REGULATION GUIDANCE: Designated operator inspection reports prior to October 1, 2018 shall be retained on <br /> site for twelve months. Designated operator inspection reports on or after October 1, 2018 shall be retained on site <br /> for thirty-six months. <br /> CORRECTIVE ACTION: Locate and ensure that copies of the previous thirty-six months of designated operator <br /> inspection reports are maintained on site. Submit copies of the missing reports to the EHD. <br /> This is a minor violation. <br /> 320 CCR 2635, 2637.2, 2665, 2712 Failure to comply with the installation, inspection, or record keeping of the overfill <br /> prevention. <br /> Overfill prevention testing has not been conducted. This testing was required to be conducted by October 13, <br /> 2018. Ensure all future testing is conducted within required time frames. <br /> This is a repeat violation, Class II. <br /> Overall Inspection Comments: <br /> An inspection report was provided to the facility operator on the day of inspection. The report was amended by <br /> the EHD. The amended report replaces the initial report. Violations# 204, 205 and 210 added, <br /> and violation 101 removed. <br /> Complete and submit a copy of the Return to Compliance Certification form to the EHD with a statement <br /> documenting the corrective actions that have been or will be taken for each violation, and any supporting <br /> paperwork, by December 14, 2019. <br /> FA0003777 PR0231014 SCO01 10/25/2019 <br /> EHD 23-01 Rev.9/20/2019 Page 6 of 7 Underground Storage Tank Program OIR <br /> 1868 E. Hazelton Avenue I Stockton, California 95205 1 T 209 468-3420 1 F 209 464-0138 1 www.sjcehd.com <br />
The URL can be used to link to this page
Your browser does not support the video tag.