Laserfiche WebLink
u Model 244 Emergency Vents 18-inch <br /> SPECIFICATION SHEET <br /> Application <br /> UL Listed emergency vent (pressure relief only) used on aboveground <br /> storage tanks, as a code requirement, to help prevent the tank from <br /> becoming over-pressurized and possibly rupturing if ever exposed to <br /> fire. The vent must be used in conjunction with a "normal vent." Correct <br /> i <br /> application of this vent requires proper vent size and selection for the <br /> tank system in order to meet the specific venting capacity. <br /> Code Compliance <br /> When properly sized for the tank, this vent will conform to the Fig.2440M <br /> C US LISTED UL <br /> U� <br /> requirements of the International Fire Code; National Fire Code of Canada; 2583 <br /> National Fire Protection Agency- NFPA 1, 30, 30A, 31, 37, 110; Petroleum <br /> Equipment Institute- PEI RP200, PEI RP800; Underwriters Laboratories Inc. <br /> UL-142, UL-2085, UL-2244; Underwriters Laboratories of Canada CAN/ <br /> ULC S601, CAN/ULC S602, CAN/ULC S652 WARNING: DO NOT FILL OR <br /> UNLOAD FUEL FROM A STORAGE <br /> TANK IT IS <br /> Approvals THAT THEESS TANK VENTSERTAIN WILL <br /> California Air Resource Board (CARB) Phase 1 Enhanced Vapor OPERATE PROPERLY. Morrison <br /> Recover EVR AST Certified Products VR-402-B tank vents are designed only for use <br /> Recovery ( ) ( ) � on shop fabricated atmospheric tanks <br /> Underwriters Laboratories Inc. UL-2583 which have been built and tested in <br /> accordance with UL 142, NFPA 30 & <br /> 30A, and API 650 and in accordance <br /> Overall with all applicable local, state, and <br /> Item Number A B C D E F G Diameter Height Weight federal laws. In normal operation, dust <br /> 2440--0600AV8" 503,517 8 1 A AL 13.5" 4.6' 33.0 and debris can accumulate in vent <br /> E1R 2440--0600AVEVR 8" 503,517 8 1 B AL 13.5" 4.6" 33.0 openings and block air passages. <br /> 2440--0700AV 8" 503,517 16 1 A AL 13.5" 5.8" 62.0 Certain atmospheric conditions such as <br /> EVRa sudden drop in temperature, below <br /> 2440--0700AVEVR 6" 503,517 16 1 B AL 13.5" 5.8" 62.0 freezing temperatures,and freezing rain <br /> l� 2440E-0100AV 8" 503,517 F 8 1 A AL 13.5" 3.3" 33.0 can cause moisture to enter the vent <br /> EVR 2440E-0100AVEVR 8" 503,517 F 8 1 B AL 13.5" 3.3" 33.0 and freeze which can restrict internal <br /> 1119 2440E-0200AV 8° 503,517 F 16 1 A AL 13.5" 4.5" 67.0 movement of vent mechanisms and <br /> EVR 2440E-0200AVEVR 8' 503,517 F 16 1 B AL 13.5" 4.5" 67.0 block air passages.All storage tank vent <br /> air passages must be completely free of <br /> E 2440M-0600AV 8" 503,517 M 8 111 <br /> 13.5" 5.8" 34.0 restriction and all vent mechanisms must <br /> 2440M-0600AVEVR 8" 503,517 M 8 13.5" 5.8° 34.0 have free movement in order to insure <br /> s 2440M-0700 AV 8" 503,517 M 16 13.5" 6.9" 63.0 proper operation. Any restriction of <br /> EVR 2440M-0700AVEVR 8" 503,517 M 16 13.5" 6.9" 63.0 airflow,can cause excessive pressure or <br /> 2440MB0700AV 8" 503,517 M 16 13.5" 6.9" 63.0 vacuum to build up in the storage tank, <br /> 2440MBSP0600AV 8" 503,517 M 8 13.5" 5.8" 34.0 which can result In structural damage <br /> to the tank, fuel spillage, property <br /> Flange=14"OD;eight(8).88"Diameter holes on 11.75"diameter B.C. damage, fire, injury, and death. Monthly <br /> SPECIFICATION OPTIONS: inspection, and immediate inspection <br /> A-Size(inches) during freezing conditions, by someone <br /> B-Venting capacity/SCFH at 2.5 P.S.I. familiar with the proper operation of <br /> C-Mounting connection:Female N.P.T.(BLANK);Male N.P.T(M);Flanged(F); storage tank vents, is required to insure <br /> D-Pressure settings:8,16 oz/in'.Pressure required to open vent. venting devices are functioning properly <br /> E-Cover:Cast iron powder coated(1) before filling or unloading a tank. <br /> F-Seat material: O-Ring Viton A(A)or Viton B(B) <br /> G-Body material:Aluminum(AL)or Iron(1) <br /> Diameter-Dimension across vent(inches) <br /> Height-Dimension from base to top when closed(inches) <br /> Weight-Shipping weight(Ibs) <br /> Bolt-Zinc plated steel <br /> S70 E.7th Street,P.O.Box 238 1 Dubuque,IA 52004-0238 <br /> t.563.583.5701 1 800.553.4840 1 f.563.583.5028 <br /> MORRISONBROS. CO. www.morbros.com <br />