Laserfiche WebLink
= 4 UST Spill Bucket <br /> SOLUTIONS OELIVERr= O Integrity Testing Form <br /> Underground Storage Tanks ( UST) Program <br /> Instructions on Page 3 <br /> Purpose : This procedure is to test the leak integrity of single = and double -walled spill buckets . See reverse <br /> side for basic hydrostatic testing instructions . Consult PEI/RP1200 , Section 6 .2 for hydrostatic test method , <br /> Section 6 . 3 for single -walled vacuum test method , and Section 6 . 4 for double -walled vacuum test method . <br /> Testing Information <br /> 1 . Tank number T2 89 T3 87 T4 Diesel <br /> 2 . Product stored Unleaded Unleaded Diesel <br /> 3 . Spill bucket capacity 5 Gallons 5 Gallons 5 Gallons <br /> 4. Manufacturer OPW OPW OPW <br /> ❑ Single -walled ❑ Single-walled ❑ Single-walled ❑ Single-walled ❑ Single -walled ❑ Single-walled <br /> 5. Construction ® Double-walled ® Double-walled ® Double-walled ® Double-walled ❑ Double-walled ❑ Double-walled <br /> ® Hydrostatic ® Hydrostatic ® Hydrostatic ❑ Hydrostatic ❑ Hydrostatic ❑ Hydrostatic <br /> ❑ Vacuum ❑ Vacuum ❑ Vacuum ❑ Vacuum ❑ Vacuum ❑ Vacuum <br /> ❑ Single-walled ❑ Single-walled ❑ Single -walled ❑ Single-walled ❑ Single-walled ❑ Single-walled <br /> 6 . Test type ❑ Double-walled ❑ Double-walled ❑ Double -walled ❑ Double-walled ❑ Double-walled ❑ Double-walled <br /> ® Product N Product ® Product ® Product ❑ Product ❑ Product <br /> 7 . Spill bucket type ❑ Vapor ❑ Vapor ❑ Vapor ❑ Vapor ❑ Vapor ❑ Vapor <br /> 8 . Liquid and debris <br /> removed from spill <br /> bucket:* ® Yes ❑ No ® Yes ❑ No ® Yes ❑ No ❑ Yes ❑ No ❑ Yes ❑ No ❑ Yes ❑ No <br /> 9. Visual inspection <br /> (No cracks, loose parts or <br /> separation of the bucket <br /> from the fill i e.)? ® Pass ❑ Fail ® Pass ❑ Fail ® Pass ❑ Fail ❑ Pass ❑ Fail ❑ Pass ❑ Fail ❑ Pass ❑ Fail <br /> 10 . Tank riser cap included in <br /> test? ® Yes ❑ No ❑ NA ® Yes ❑ No ❑ NA ® Yes ❑ No ❑ NA ❑ Yes ❑ No ❑ NA ❑ Yes ❑ No ❑ NA ❑ Yes ❑ No ❑ NA <br /> 11 . Is drain valve included in <br /> test? ® Yes ❑ No ❑ NA ® Yes ❑ No ❑ NA ® Yes ❑ No ❑ NA ❑ Yes ❑ No ❑ NA ❑ Yes ❑ No ❑ NA ❑ Yes ❑ No ❑ NA <br /> 12. Starting level 13 .50" 13.50" 13.50" <br /> 13. Test start time 10 : 00am 10 : 00am 10 : 00am <br /> 14. Ending level 13.50" 13.50" 13.50" <br /> 15. Test end time 11 : 00am 11 :00am 11 : 00am <br /> 16. Test period 1 hour 1 hour 1 hour <br /> 16. Level chane 0 0 0 <br /> Test results : ® Pass ❑ Fail ® Pass ❑ Fail ® Pass ❑ Fail ❑ Pass ❑ Fail ❑ Pass ❑ Fail ❑ Pass ❑ Fail <br /> Pass/fail criteria: Must pass visual inspection. Hydrostatic: Water level drop of less than 1/8 inch; Vacuum single-walled <br /> only; Maintain at least 26 inches water column; Vacuum double-walled; maintain at least 12 inches water column. <br /> Comments : <br /> * All liquids and debris must be disposed of properly. <br /> Testing company <br /> name : CGRS Tester's name : Garrett Warren <br /> Date : 1 -8 -2020 Tester's signature : <br />